Configuring test stop

Test stop
The test stop of the basic functions is a self-test of the inverter in order to test the circuits for
the safe torque off. The test stop is restarted after each selection of the STO function and
after the connection of the supply voltage (switch on). A time block monitors whether the test
stop is performed regularly.
1. Click "Test stop" in the secondary navigation.
2. In the opened screen, enter the duration of the time interval in which the test stop must be
performed.
Figure 9-6
3. You can specify the time interval. The permitted maximum value is 8760 hours (one year)
that is normally determined with a risk analysis. Eight hours are entered as default
setting. Alarm A1699 (test stop required) is issued when the time interval expires.
Note
The remaining time until the occurrence of the alarm A1699 is also displayed in the
screen. This timer is reset for each test stop to the previously configured value.
You have now configured the test stop of the basic functions.