Graco Gateway Configuration

1. Ethernet Settings. Set the IP Address to
192.168.2.101. This should match the Address/Host
Name entered in F
IG
2. Protocol Settings. Select the Ethernet/IP Slave
Adapter communications driver.
The ENET/B module prefixes all output data with a
header containing status information about the orig-
inator's run/idle state. With the Run/Idle Header
checked, the communications driver will automati-
cally process the header, and data will be ignored if
the device is in the Idle state. With the option
unchecked, extra space must be allocated in the
Gateway block to receive the status information; all
data is accepted regardless of the device state.
F
. 74. Ethernet Block Settings
IG
312785B
. 72.
Appendix C: Graco Gateway to ControlLogix via Ethernet IP
3. Device Settings. A Gateway block must be created
for each connection point.
For the purpose of configuring, the data transfer
terms input and output are relative to the device and
not the Gateway. An input connection is therefore
specified as Gateway to Device, and an output con-
nection is specified as Device to Gateway.
Connection point mapping is defined in the Start
Address block setting and comprises the connection
point instance and a data offset. The instance must
match that specified by the originator; the offset can
be used to skip over data not required by the Gate-
way, useful mainly on shared connection points.
77