Commissioning; Data Communication Via Profibus-Dp; Structure Of The User Data In The Profibus-Dp Message Frame - Siemens CB15 Operating Instructions Manual

Profibus module
Table of Contents

Advertisement

PROFIBUS MODULE (CB15/CB155)

5. COMMISSIONING

5.1 Data Communication via PROFIBUS-DP

The structure of the user data is designated as parameter process data objects (PPO) in the PROFIBUS variable
speed drives profile:
Protocol Frame
(Header)
Figure 2: Structure of the User Data in the PROFIBUS-DP Message Frame
There is user data with a parameter area (PKW) and a process data area (PZD) and user data that consists
exclusively of process data. The PROFIBUS variable speed drives profile defines five PPO types. The PPO type is
defined in the PROFIBUS-DP master parameter settings.
PKW
PKE IND
1st
2nd
Word
Word
PPO1
PPO2
PPO3
PPO4
PPO5
PKW:
Parameter identifier value
PZD:
Process data
PKE:
Parameter identifier
IND:
Index
PWE:
Parameter value
STW1:
Control word 1
ZSW1:
Status word 1
HSW:
Main setpoint
HIW:
Main actual value
Figure 3: Parameter Process Data Object (PPO Types)
Note
The CB15/CB155 only supports PPO types 1 and 3.
Parameter (PKW)
PZD
PWE
PZD1
PZD2
STW1
HSW
ZSW1
HIW
3rd
4th
1st Word
2nd
Word
Word
Word
U s e r D a t a
Process Data (PZD)
PZD
PZD
PZD
PZD
3
4
5
3rd
4th
5th
Word
Word
Word
14
Operating Instructions
Protocol Frame
(Trailer)
PZD
PZD
PZD
6
7
8
9
6th
7th
8th
9th
Word
Word
Word
Word
English
PZD1
0
10th
Word

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cb155

Table of Contents