PROFIBUS MODULE (CB15/CB155)

3. OPERATING INFORMATION

3.1 Local Control

The inverter will operate a motor in an identical manner to that described in the operating instructions for the
inverter.
Note
An on/off switch must always be fitted to allow the motor to be switched on and off locally.

3.2 Remote Control

Different modes of remote control are available via the serial link (refer to parameters P927 and P928 in section
3.3.2 for details) .

3.3 System Parameters

The basic parameter set used by the CB15/CB155 is identical to that used for the inverter. However, some
parameters cannot be accessed because either they are not required or they have been replaced by PROFIBUS
parameters.

3.3.1 Parameters not Available via the CB15/CB155

P091
Slave address (replaced by P918)
P092
Baud rate (replaced by P963)
P093
USS Timeout
P121 - P124
Enable/Disable control keys
P910
Local/Remote mode (replaced by P927 and P928)
P922
Software version (replaced by P702)
P923
Equipment system number (replaced by P701)
P930
Fault log (replaced by P947)
P931
Warning (replaced by P958)

3.3.2 Parameters Specific to the CB15/CB155

Note
_ = Parameter can be changed during operation.
Parameter
Function
P700
Software version, PROFIBUS
module
P701 _
Equipment system number
Software version
P702
P880
Indexed parameter
diagnostic data
P918 _
PROFIBUS-DP slave
address
P927 _
PROFIBUS-DP local/remote
parameter control
Range
Description / Notes
[Default]
00.00 - 99.99
Contains the software version number of the PROFIBUS module and
[-]
cannot be changed.
0 - 255
You can use this parameter to allocate a unique reference number to
[0]
the inverter. It has no operational effect.
00.00 - 99.99
Contains the software version number of the inverter and cannot be
[-]
changed.
-
This parameter contains data relating to the PROFIBUS-DP function
(see section 6.1).
1 - 126
Sets the bus address (range 1 to 126) for the RS485 serial interface
[126]
with PROFIBUS-DP protocol.
0 - 1
Sets local or remote parameter control via the RS485 interface:
[0]
0 = Local parameter control
1 = Remote parameter control
11
English
Operating Instructions