Recommended Spare Parts; Decommissioning And Disposal Of The Components And Machine - Mitsubishi Electric CLIMAVENETA Series General Manual For Installation

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 19
C0210101-07-16-EN
EnviroCoil Universal Coil Cleaner
Attention!
Do not use high pressure cleaners to clean the coil as excessive pressure can cause irreparable damage. Damage caused by cleaning with
chemical substances or excessive water pressure is not covered by the guarantee.
Attention!
Make sure to always wear appropriate PPE to avoid cuts and abrasions. Protect the eyes and face against the spraying of water and dirt
during the cleaning process. Wear waterproof shoes or boots and clothes that cover all the body.
12.4 Cleaning the components that exchange heat with water or water solutions
Entrust cleaning of the heat exchangers to specialised companies who will use chemical substances compatible with the materials of the
exchanger.
Where the water flows in tubes, any mechanical cleaning must be carried out using only soft nylon brushes. This is because metal brushes can
damage and, therefore, reduce the efficiency of the fins in the tubes, and damage the protective layer of oxide thereby increasing the risk of
corrosion.
13

RECOMMENDED SPARE PARTS

The list of spare parts is provided on request.
13.1 1 year
Fuse
Dehydrator filters
Solenoid valve coils
Air filters
Water differential pressure switch
Belts
Probes
Casing resistances
13.2 2 years
In addition to the 1 year list:
Pressure switches
Safety valves
Contactors and auxiliary relays
Compressor thermal overload cut-outs
Automatic circuit breakers
Transducers
Fans
13.3 5 years
In addition to the 1 year and 2 year lists:
Solenoid valves
Thermostat valves
Pressure gauges
Compressors
Electronic components
Fans
Set of condensers for centrifugal compressor
14

DECOMMISSIONING AND DISPOSAL OF THE COMPONENTS AND MACHINE

WARNING! The unit contains fluorinated greenhouse gases covered by the Kyoto protocol. In accordance with the law, these must not be
dispersed in the environment but collected and delivered to the retailer or collection centre.
When components are replaced, or when the entire unit is removed from the installation at the end of its useful life, the following requirements must
be observed to minimise impact on the environment:
the refrigerant gas must all be collected by specialist personnel with the necessary certification and delivered to the collection centres;
the lubrication oil in the compressors and cooling circuit must be collected and delivered to the collection centres;
the structure, the electrical and electronic equipment and the components must be sorted according to category and material and delivered to
the collection centres;
if the water circuit contains mixtures with antifreeze, these must be collected and delivered to the collection centres;
observe the domestic laws in force.
Advanced Engineering
all
all
1 per type
all
1 per type
all
1 per type
1 per type
all
all
all
all
all
all
1 per type
all
all
all
1 per type
all
50% of the number per type
/
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents