Chapter 3: StorEdge Interface Installation

Chapter 3: StorEdge Interface Installation

Unpacking and Identifying the Product

An identification label with product specifications is attached to each device.
Check the equipment for damage before starting installation: There are no loose parts. All parts are either 
mounted or located in the accessory kit. If any damage is found, document the damage, and contact 
SolarEdge.

Mounting the StorEdge Interface

 1.  Determine the StorEdge Interface mounting location, on a wall or pole, as follows:
 
Maximum distance from the battery: 5m (15 ft)
l
 
Maximum distance   f rom the inverter: 100m (328 ft)
l
 
Maintain a minimum 20 cm (8") clearance between the   S torEdge Interface and other objects.
l
 2.  Install the bracket with the semi-circles facing down, as shown below. Verify that the bracket is firmly 
attached to the mounting surface.
 3.  Install the interface: Attach the StorEdge interface back brackets to the mounted bracket using the 
four supplied screws. Tighten the screws with a torque of 9 N*m / 6.6 lb*ft.
 4.  Loosen the 4 Allen screws of the StorEdge Interface and remove the cover.
10
Figure 7: StorEdge Interface clearance
Figure 8: Mounting bracket
Figure 9: The StorEdge Interface
StorEdge Interface Installation Guide MAN-01-00380-1.1