Software Upgrades - Eaton VoCALL 16 Installation And Operation Manual

Emergency voice communication system standalone configuration
Table of Contents

Advertisement

15. Software upgrades

Software upgrades should only be performed by a competent trained Engineer.
n
ote:
During a software upgrade system will be put in engineering mode and no
calls will be allowed to be made. Liaise with the building manager.
Updated software release files would be available with Engineer or from Eaton.
Perform below steps to update the software.
1. Remove mains supply. Panel would now be powered using battery.
2. Open the top cover of panel.
3. Remove the SD card. Copy the release files in UPDATES folder on SD Card.
The files would have '.aes' extension
4. Safely eject the SD Card. Plug the SD Card back in socket provided.
5. Close the top cover. Power up the panel.
6. Login as 'Engineer 2'
7 . Go to menu option 'Install'
8. Go to option 'update Software'
ENGINEER 2
7 Manage Users
8 Display Settings
9 System Time / Date
10 System Service Date
11 Install
12 Test
9. Select the file from the list for upgrade.
10. Panel will ask for confirmation to perform the upgrade.
Update Software
1 Outstation A,B
11. After upgrade, go to option 'panel Information' and verify the software revision.
InStALLAtIon And opErAtIon mAnuAL 25-13741-E January 2020 www.eaton.com
(11-13)
1 System Settings
2 names
3 Outstation Learn
4 Update Software
5 Factory Defaults
v1.51
1 System Settings
2 names
3 Outstation Learn
4 Update Software
5 Factory Defaults
15. Software upgrades
Install
Install
Do you really want
to update software?
Yes =
No =
(4-5)