Electro-Magnetic Compatibility (Emc); Compatibility With Rcds - Siemens BT300 Manual

Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Safety
1.4

Electro-magnetic compatibility (EMC)

This equipment complies with IEC 61000-3-12 provided that the short-circuit power S
or equal to 120 at the interface point between the user's supply and the public system. It is the respon-
sibility of the installer or user of the equipment to ensure, by consultation with the distribution network
operator if necessary, that the equipment is connected only to a supply with a short-circuit power S
greater than or equal to 120.
1.5

Compatibility with RCDs

If a fault protection relay is used, it must be of at least type B, preferably B+ (according to
EN 50178), with a trip level of 300 mA. This is for protection, not for touch protection in
grounded systems.