Technical data
Ambient conditions
Vibrations
EMC (at default set-
tings)
Noise level
Safety
24-hour support +1-800-877-7545 (Dial 2)
Table 32. Siemens BT300 Technical Data
Ambient operating tem-
perature
Storage temperature
Relative humidity
Air quality:
chemical vapors
mechanical particles
Altitude
Vibration
EN61800-5-1/EN60068-2-
6
Shock
EN61800-5-1
EN60068-2-27
Enclosure class
Immunity
Emissions
Average noise level (cool-
ing fan) sound power level
in dB(A)
I
: -10 °C (14 °F) (no frost)...+40 °C (86 °F); up to
L
+50 °C (122 °F) with derating
-40 °C (-40 °F)...+70 °C (158 °F)
0...95% R
, non-condensing, non-corrosive
H
Tested according to IEC 60068-2-60 Test Ke:
Flowing mixed gas corrosion test, Method 1 (H
[hydrogen sulfide] and SO
Designed according to:
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 1,000 m
(3,280 ft)
1-% derating for each 100 m (328 ft) above
1,000 m (3,280 ft)
Max. altitudes:
208...240 V: 4,500 m (14,764 ft) (TN and IT sys-
tems)
380...480 V: 4,500 m (14,764 ft) (TN and IT sys-
tems)
Voltage for relay outputs:
Up to 2,000 m (6,562 ft): Allowed up to 240 V
2,000 m (6,562 ft)...4,500 m (14,764 ft): Allowed
up to 120 V
Corner-grounding:
up to 2,000 m (6,562 ft) only.
5...150 Hz
Displacement amplitude 1 mm (0.04 in) (peak)
at 5...15.8 Hz (FS4...FS9)
Max acceleration amplitude 1 G
at 15.8...150 Hz (FS4...FS9)
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in pack-
age)
Type 1/IP21 standard in entire kW/HP range
Type 12/IP54 option
NOTE: Keypad required for Type 12/IP54
Fulfills EN61800-3 (2004), first and second envi-
ronment
+EMC2: EN61800-3 (2004), Category C2
The drive can be modified for IT-networks. See
Chapter 6.3 on page 62.
FS4: 65
FS7: 77
FS5: 70
FS8: 86
FS6: 77
FS9: 87
EN 61800-5-1 (2007), CE, cUL; (see unit name-
plate for more detailed approvals)
Siemens Industry, Inc • 71
[sulfur dioxide])
2
S
2