3 = Symmetrical power cable equipped with compact low-impedance shield and intended
for the specific mains voltage. [MCCMK, EMCMK or similar recommended; Recom-
mended cable transfer impedance (1...30MHz) max. 100mohm/m). See Figure 17.
*360º earthing of the shield with cable glands in motor end needed for EMC level C2.
4 = Screened cable equipped with compact low-impedance shield (JAMAK, SAB/ÖZCuY-O
or similar).
NOTE
: The EMC requirements are fulfilled at factory defaults of switching frequencies (all frames).
NOTE:
If safety switch is connected the EMC, protection shall be continuous over the whole cable in-
stallation.
4.1

UL standards on cabling

To meet the UL (Underwriters Laboratories) regulations, use a UL approved copper cable with a mini-
mum heat-resistance of +60/75 °C (75/167 °F). Use Class 1 wire only.
The units are suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical
amperes, 600 V maximum.
4.1.1

Cable dimensioning and selection

Table 15 shows the minimum dimensions of the Cu/Al-cables and the corresponding fuse sizes.
These instructions apply only to cases with one motor and one cable connection from the AC drive to
the motor. In any other case, ask the factory for more information.
PE conductor
and shield
9007.emf
PE conductors
Shield
Figure 17.
24-hour support +1-800-877-7545 (Dial 2)
Power cabling