Commissioning
6.3.1
Frames FS4 to FS6
1
Remove the main cover of the drive (see page 30) and locate the jumpers connecting the
built-in RFI-filters to ground. See Figure 53.
FS4
Figure 53. Locations of the EMC-jumpers in frames FS4 to FS6.
2
Disconnect the RFI-filters from ground by removing the EMC-jumpers using long-nose pli-
ers or similar. See Figure 54.
24-hour support +1-800-877-7545 (Dial 2)
FS5
Figure 54. Removing the jumper, FS5 as example.
Siemens Industry, Inc. • 63
FS6
9064bt
9060.emf