Power cabling
4.1.1.3
Cable and fuse sizes, frames FS4 to FS6
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse voltage rating
should be selected according to the supply network. The final selection should be made according to
local regulations, cable installation conditions and cable specification. Bigger fuses than what is recom-
mended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used fuse type
and impedance of the supply circuit. Consult the factory about faster fuses. Siemens offers recommen-
dations also for fast acting J (UL & CSA ), aR (UL recognized, IEC 60269-4) and gS (IEC 60269-4) fuse
ranges.
Table 17. Cable and fuse sizes for Siemens BT300 (FS4 to FS6).
Frame
Type*
001X2
00154
002X4
002X2
FS4
003X4
003X2
005X4
00754
005X2
010X4
00752
FS5
015X4
010X2
020X4
025X4
015X2
FS6
030X4
020X2
040X4
* See Figure1:Type designation codes, in Chapter 2.
The cable dimensioning is based on the criteria of the International Standard IEC60364-5-52.
Cables must be PVC-isolated; Max ambient temperature +30 °C (86 °F), max temperature of cable
surface +70 °C (158 °F); Use only cables with concentric copper shield; Max number of parallel cables
is 9.
NOTE: When using cables in parallel, the requirements of both the cross-sectional area and the max
number of cables must be observed.
For important information on the requirements of the earthing conductor, see chapter "Earthing and earth
fault protection" on page 5 of the standard.
For the correction factors for each temperature, see International Standard IEC60364-5-52.
24-hour support +1-800-877-7545 (Dial 2)
Fuse
I
L
(gG/gL)
[A]
[A]
4.8
3.4
6
4.8
6.6—8.0
10
5.6
11.0
9.6
16
12.0
18.0
20
16.0
24.0
25
23.0
31.0
32
31.0
38.0
40
48.0
50
46.0
62.0
63
61.0
Mains and
motor cable
Main terminal
2
Cu [mm
]
1—6 solid
3*1.5+1.5
1—4 stranded
1—4 stranded
1—6 solid
3*1.5+1.5
1—4 stranded
1—6 solid
3*2.5+2.5
1—4 stranded
1—4 stranded
3*6+6
1—10 Cu
3*6+6
1—10 Cu
3*10+10
1—10 Cu
3*10+10
2.5—50 Cu/Al
3*16+16 (Cu)
2.5—50 Cu/Al
3*25+16 (Al)
3*25+16 (Cu)
2.5—50 Cu/Al
3*35+10 (Al)
Siemens Industry, Inc. • 27
Terminal cable size
Earth
terminal
2
[mm
]
2
[mm
]
1—6
1—6
1—6
1—10
1—10
1—10
2.5—35
2.5—35
2.5—35