Samson TROVIS 5400 Series Mounting And Operating Instructions page 53

District heating controller
Table of Contents

Advertisement

Heating up of drinking water
Setpoint values
Requirement ON (20 to 90) [40] °C
Requirement OFF (20 to 90) [45] °C
Differential gap (0 to 30) [5] °C
(only when CO2 FB 2 = OFF)
Charging/setpoint temperature (20 to 90) [55] °C
TLP OFF (20 to 90) [48] °C
SLP OFF (20 to 90) [48] °C
(only when CO2 FB 3 = ON)
Return flow limiting (20 to 90) [45] °C
Max. flow temp. for heating up of drinking
water (20 to 120) [120] °C
(only when CO2 FB 3 = ON)
Thermal disinfection
Daily disinfection (0)
Weekly disinfection (1 – 7 = Mo – So)
Usage times heating up of drinking water (0000 to 2400 hrs)
Mon
Start 1
End 1
Start 2
End 2
Start 3
End 3
Time data circulation pump (0000 to 2400 hrs)
Mon
Start 1
End 1
Start 2
Tue
Wed
Tue
Wed
Thu
Fri
Thu
Fri
Sat
Sun
Sat
Sun
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Trovis 5430

Table of Contents