Pump lag time
Press
the symbol blinks
Press
to alter lag time
Press
and accept the value entered
End appears in the display, heating loop data entry in the parameter level PA1 is complete
Press
PA2 appears in the display, the parameter level for entry of data for heating up
of drinking water
Parameter level PA2 entries
Drinking water requirement ON
followed by
Differential gap
Press
the symbols blink
Press
set temperature
Press
the value is accepted
Drinking water requirement ON
followed by
Drinking water requirement OFF
Press
the symbols blink
Press
set temperature
Press
the value is accepted
Enter the following display values in the same manner.
46
(60 to 600 secs)
(20 to 90 °C)
on system 2 and 3 with only
one storage tank sensor SF1
(0 to 30 °C)
(20 to 90 °C)
on system 2 and 3 with
two storage tank sensors
SF1 and SF2
(CO2 FB 1 = ON, FB 2 = ON)
(20 to 90 °C)