Samson TROVIS 5400 Series Mounting And Operating Instructions page 42

District heating controller
Table of Contents

Advertisement

Heating characteristic level
Parallel adjustment of the heating characteristic, upwards (positive value) or downwards
(negative value) (–30...+30°C).
If a modification is desired:
Press
the parameter blinks
Press
and enter the desired adjustment value in °C
Press
the value is accepted
Characteristics according to 4 points (CO1 FB 4 = ON)
Press
to access parameter level PA1, the menu for the characteristic appears
Outdoor temperature
1st point
Press
display the next value or
Press
the symbol blinks
Press
adjust to the desired value
Press
the value is accepted
Flow temperature
1st point
Return flow temperature
1st point
Points 2 to 4 are entered in the same way. The corresponding point is marked by a square to the
right below numbers 1 to 4.
Default setting °C
Outdoor temperature
Flow temperature
Return flow temperature
Reduced temperature
2nd and 3rd point
The reducing temperature at point 2 and point 3 is entered in the same manner. The correspon-
ding point is marked by a square to the right below numbers 2 or 3.
42
point 1
point 2
–15
–5
70
55
65
50
point 3
point 4
5
15
40
25
35
20