Samson TROVIS 5400 Series Mounting And Operating Instructions page 20

District heating controller
Table of Contents

Advertisement

B) The temperature at the flow sensor is less than the charging temperature setpoint value, but
higher than 40 °C
If the temperature in the storage tank falls below the value for drinking water requirement ON at
sensor SF1 or if the temperature falls below the value set at the storage tank thermostat, com-
mencement of storage tank charging initially only leads to a buildup of the charging temperatu-
re via the heating loop.
At 5K below the charging setpoint value (measured at flow sensor VF), the SLP starts up. At the
same time the UP is switched off; the ZP runs according to the function block setting.
If the requirement is terminated by exceeding the adjustable differential gap at sensor SF1 or the
preset differential gap at the storage tank thermostat, the controller initially runs at a fixed defi-
nable value at sensor VF. When this is attained, at the latest after two running periods of the con-
trol valve, the UP is switched on and the SLP is switched off. The ZP runs according to a time pro-
gram.
C) The temperature at the flow sensor is less than 40 °C
If the temperature in the storage tank falls below the value for drinking water requirement ON at
sensor SF1 or if the temperature falls below the value set at the storage tank thermostat, com-
mencement of storage tank charging leads to an immediate buildup of the charging temperature
via the storage tank, i.e. the UP is switched off and the SLP is switched on. The ZP runs according
to the function block setting.
If the requirement is terminated by exceeding the adjustable differential gap at sensor SF1 or the
preset differential gap at the storage tank thermostat, the controller operates again according to
the heating characteristic; while the control valve is closing, the flow temperature is monitored at
sensor VF. If this is reduced down to a fixed definable value, at the latest however after two run-
ning periods of the control valve, the UP is switched on and the SLP is switched off. The ZP runs
according to a time program.
D) Summertime operation or switched off operation
If the temperature in the storage tank falls below the value for drinking water requirement ON at
sensor SF1 or if the temperature falls below the value set at the storage tank thermostat, com-
mencement of storage tank charging leads to an immediate buildup of the charging temperature
via the storage tank, i.e. the SLP is switched on. The ZP runs according to the function block set-
ting.
If CO2 FB 8 = ON, the SLP is only switched on when the temperature at sensor RüF is higher than
the temperature at sensor SF1.
When the requirement is terminated, the control valve is closed. While the control valve is clo-
sing, the flow temperature is monitored at sensor VF. If this is reduced down to a fixed definable
value, at the latest however after two running periods of the control valve, the UP is switched on
and the SLP is switched off. The ZP runs according to a time program.