I/O Wiring – FM CIO Transmitters
Table 7-1
Channel configuration
Channel
A
B
C
(1) The Bell 202 signal is superimposed on the mA output.
(2) You must provide power to the outputs when a channel is set to external power.
(3) When configured for two frequency outputs (dual pulse), frequency output 2 is generated from the same signal that is sent
to the first frequency output. Frequency output 2 is electrically isolated but not independent.
Figure 7-1
Configuration of configurable I/O terminals
Terminals 1 and 2 (Channel A)
mA1 output
Internal power only
HART (Bell 202) communications
Terminals 3 and 4 (Channel B)
mA2 output OR FO OR DO1
Power:
mA – internal only
FO or DO – internal or external
No communications
Terminals 5 and 6 (Channel C)
FO OR DO2 OR DI
Power: internal or external
No communications
mA = milliamp
FO = frequency output
DO = discrete output
DI = discrete input
7.3

mA output wiring

The following 4–20 mA wiring diagrams are examples of proper basic wiring for the LF-Series FM
CIO transmitter's primary and secondary mA outputs. The following options are shown:
Basic mA wiring (Figure 7-2)
HART/analog single-loop wiring (Figure 7-3)
HART multidrop wiring (Figure 7-4)
32
Terminals
Configuration options
1 & 2
mA output with HART/Bell 202
3 & 4
• mA output (default)
• Frequency output
• Discrete output
5 & 6
• Frequency output (default)
• Discrete output
• Discrete input
(1)
(3)
+
+
+
LF-Series Flowmeters: Sensor/Transmitter Installation
Power
Internal
Internal
(2)
Internal or external
Internal or external
Internal or external
Internal or external
Internal or external