baltur COMIST 180 Manual Installation, Use, Maintenance page 49

Dual fuel burners gas / light oil
Hide thumbs Also See for COMIST 180:
Table of Contents

Advertisement

Available languages

Available languages

TABLE OF PIPELINE FOR COMIST 180
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
GRAVITY FEED SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
Pump axis
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
Pump axis
SUCTION FEED SYSTEM
Pump axis
N.B. Comply with existing regulations
regarding apparatus required in the
pipeline system
H - Height difference between minimum fuel tank level and pump axis.
L - Total length of pipeline, including vertical lenght. Subtract 0,25 mt.
for every elbow or gate valve.
0006080095_200902
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
H
meters
1
1,5
2
2,5
3
8 Automatic fuel interception
device at burner shut off
9 One-way valve
10 Bottom valve
H
meters
1
1,5
2
2,5
3
H
meters
0,5
1
1,5
2
2,5
3
3,5
11 / 34
Total lenght
meters
Ø i. 16 mm.
Ø i. 18 mm.
30
40
35
45
35
45
40
50
40
50
Total lenght
meters
Ø i. 16 mm.
Ø i. 18 mm.
30
40
35
45
35
45
40
50
40
50
Dimension P = 3,5 m. (max.)
Total lenght
meters
Ø i. 16 mm.
Ø i. 18 mm.
21
34
18
29
15
24
11,5
19
8,5
14
5,5
9
-
3,5