Voltage
Power
Regulation
Factor
0.9 lag
±1%
3) Operating Environment
Temperature
0°C-45°C
Note: if the UPS is installed or used in a place where the altitude is
above than 1000m, the output power must be derated in use, please
refer to the following:
Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Maximum
100% 95%
Power
Output
Frequency
Distortion
tolerance.
Synchronized
THD<2%
50/60Hz±10%
Full load
in Line mode
(Linear
(AC mode)
Load)/
<5% for
±0.1% of
reference
normal
non-linear
frequency in
load
Battery mode
Humidity
<95%
91%
86%
12
Overload capacity
100%-110% load
transfers to Bypass
mode after 5
minutes
110%-130% load
transfers to Bypass
mode after 1
minutes
130%-150% load
transfers to Bypass
mode after 10
second
>150% load
transfers to Bypass
mode after 2 second
Altitude
Storage temperature
<1000m
82%
78%
74%
Current
crest ratio
3:1
-15°C-50°C
70%
67%