Table A-1 Technical Specifications
Category
Environmental
conditions
AC input
DC output
Issue 04 (2019-12-20)
A
Item
Operating temperature
Storage temperature
Transportation
temperature
Operating humidity
Storage humidity
Altitude
Input mode
Input voltage
Input frequency
Power factor
Output voltage range
Default output voltage
Maximum output
power
Regulated voltage
precision
Peak-to-peak noise
voltage
Others
Copyright © Huawei Technologies Co., Ltd.
Technical Specifications
Specifications
–10º C to +50º C (+14º F to +122º F)
–40° C to +70° C (–40° F to +158° F)
–40° C to +70° C (–40° F to +158° F)
5%–95% RH (non-condensing)
5%–95% RH (non-condensing)
0–4000 m (0- 13123.2 ft)
When the altitude ranges from 3000 m (9842.4 ft) to 4000 m
(13123.2 ft), the operating temperature is derated by 1º C
(1.8º F) for each additional 100 m (328.08 ft).
Single phase three wire (L, N, and PE)
90–290 V AC (rated voltage: 220 V AC)
40–65 Hz (rated frequency: 50/60 Hz)
≥ 0.99 (rated load)
–42 V DC to –58V DC
–53.5 V DC
Number of rectifiers multiplied by the output power of a
single rectifier
≤ 1%
≤ 200 mV (0–20 MHz)
No damage is caused if a storage battery is connected
reversely.

A Technical Specifications