Chapter 6 Features; Bootloader Mode; Firmware Update; Technical Information - Gude Expert Power Control NET 8x 8211 Manual

Table of Contents

Advertisement

Expert Power Control NET 8x 8210 / 8211
6
Features
6.1

Bootloader mode

To activate the bootloader mode of Expert Power Control NET 8x 8210 / 8211 the select button must be pushed while
restarting the device. In bootloader mode it is possible to disable the password protection, to update the firmware and to
restore the default settings by running the program GBL_Conf.exe.
If the device runs already, press the buttons "select" and "ok" for three seconds. The bootloader mode of Expert Power
Control NET 8x 8210 / 8211 is indicated by "BOOT-LDR" appended to the device name in the program window of GBL_Conf.
exe.
During bootloader mode an alteration of the relais is not possible.
To restart the firmware, without toggle the Power Ports, press the buttons select and ok for three seconds again.
6.2

Firmware update

In order to update the firmware the program GBL_Conf.exe and the latest firmware are needed.
Start the device in bootloader mode and run the program GBL_Conf.exe. On the left side of the program window all Gude
devices that are in the network are listed. Select the device, that should be updated, click on Program DeviceFirmware
Update and determine the location of the new firmware.
Please note: The up-to-date firmware and GBL_Conf.exe can be found at www.gude.info, free to download.
6.3

Technical information

Connections:
Network:
Protocols:
Switched Power (total):
Switched Power (per port):
Power supply:
Operating temperature:
Dimensions:
Total weight:
6.4
Fabrique settings
In order to restore the default settings the device must be started in bootloader mode. Besides that the program GBL_Conf.
exe is required.
Run GBL_Conf.exe and select the device whose settings should be restored. Then click on Program Device -> Reset to Fab
default.
Please notice that all current settings will be deleted. The default settings will be loaded when the firmware of the device is
restarted the next time.
1 x Ethernet (RJ45)
2 x PS2 Connector
8 x Power Ports (IEC C13, max. 10A)
1 x Power supply inlet (IEC C20, max. 16A)
10/100 MBit/s 10baseT Ethernet
TCP/IP, HTTP,
SNMP v1 und v2c, SNMP traps, Syslog
16 A (~ 3600W)
10 A (~ 2000W)
IEC C20 (16A, 230V AC)
0°C-50°C
19'' / 1 rack unit
ca. 1,5 kg
21
Operation

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Expert Power Control NET 8x 8211 and is the answer not in the manual?

This manual is also suitable for:

Expert power control net 8x 8210

Table of Contents