The following table contains a description of the functions associated with the extinction that can be programmed for
the control panel inputs and outputs (on-board or on loops, through supervised outputs, such as those of the EM312SR
modules).
Terminal function
Pressure
Input for the supervision of the pressure
switch
of the cylinders containing the gas.
Confirm
Input, for the connection of a pressure
release from
switch, confirming the release of the gas
pressure
switch
Input, for the connection of a flow
Flow switch
sensor that will signal the release of the
The inputs stop the extinction procedure
Stop
in accordance with the activation mode
extinction
This input is for the connection of one or
Manual
more manual call points for the
extinction
activation of extinguishing-agent
Output for the connection of the
Electrovalve
electrovalve which discharges the
Stop
Output for the connection of stop-
extinction
active
Output for the connection of a signal
Pre-
relating to imminent discharge of the
Extinguishing
Output for the connection of signalling
devices which warn building inhabitants
Release
of the actual discharge of the
14
from the cylinders.
gas from the cylinders.
described opposite.
discharge.
extinguishing agent.
extinction signalling devices.
extinguishing agent.
extinguishing agent.
The input is activated in the case of pressure drop in the cylinders.
During stand-by status, its activation generates a fault warning.
After releasing the electrovalve, its activation is used to confirm the
release of the gas.
The input will be activated by a sensor that detects the flow of
extinguishing gas.
The flow may have been activated directly without following the
procedure of extinction and pre-extinction.
If this input is activated during the pre-extinguishment
phase, the extinguishment procedure will be aborted
Abort
The procedure can be restarted only after control panel
If this input is activated during stand-by, it will generate a
If this input activated during pre-extinguishment status,
the extinguishment procedure will remain locked until
the input resets. On input reset the pre-extinguishment
Add
countdown will refresh and restart.
If this input is activated during stand-by, it will generate a
If activated during a pre-extinction condition, the
extinction procedure is stopped but the pre-extinction
time count continues. When the input is restored, if the
Hold
pre-extinction time count has terminated, the gas will be
If this input is activated during stand-by, it will generate a
This function is identical to the "Hold" function but refers
to mechanical or electrical intervention (for example, a
door contact that inhibits gas discharge, etc.).
External
This activation will be signalled separately.
If activated during stand-by, it will not generate a fault
It will activate only when the pre-extinguishment time expires
It will activate when the extinction channel is stopped by one or
more inputs connected to the "Stop extinction" input.
It will activate during the pre-extinguishment time which runs before
the discharge of the extinguishing agent.
It will activate on activation of the electrovalve.
Fire detection and extinguishant system
Activation
even if the input resets.
reset.
fault warning.
fault warning.
released.
fault warning.
warning.