Automatic Self Test; Manual Self Test - Bender ISOMETER iso1685DP Manual

Insulation monitoring device
Hide thumbs Also See for ISOMETER iso1685DP:
Table of Contents

Advertisement

Function

3.5.2 Automatic self test

All supply voltages are continuously monitored. The following tests are continuously car-
ried out in the background:
• Connection E-KE
• Temperature monitoring of coupling and locating current injector
A self test is automatically run at 24-hour intervals.
During the automatic self test, the alarm relays K1 (11-12-14) and K2 (21-22-24) are not
switched. K3 won't be switched either.

3.5.3 Manual self test

The self test is started via the Test button of the ISOMETER®.
The following tests are only carried out in the manual self test mode:
• Internal Flash
• CPU register
• Watchdogs
• Oscillator
• Restart of the device including re-initialisation and recalibration
• Connection monitoring system
During the manual self test, all alarm relays are switched.
16
Function
iso1685DP_D00272_02_M_XXEN/07.2017

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ISOMETER iso1685DP and is the answer not in the manual?

Table of Contents