Installation

5.2 Tools

Installation
Install the expansion module before starting up the SENTRON PAC3200.
5.2
Tools
You require the following tools for installation:
● Cutting tool for the panel cutout
● Screwdriver PH2 cal. ISO 6789
Additional installation tools
You also require a self-adhesive cable clamp for strain relief.
5.3

Mounting dimensions

Mounting and clearance dimensions
You can find information on the cutout dimensions, frame dimensions and clearances in the
Chapter "Dimension drawings".
See also
Dimension drawings (Page 167)
5.4

Installation steps

Proceed as follows to install the SENTRON PAC3200 in the switching panel:
Procedure
1. Cut a hole in the panel measuring 92.0
2. Discharge any static from your body. Observe the ESD guidelines in the Appendix.
3. Insert the device into the cutout from outside (Fig. "Installation cutout A").
4. Carry out all other installation steps from the inside of the switching panel.
68
CAUTION
Electrostatic sensitive devices
Discharge your body of any static electricity! Touch the grounded control cabinet, for
example, or a metal part that is connected to the building ground (heater, steel support).
x 92.0
mm
(if not already available).
+0.8
+0.8