Technical data
11.1 Technical data
Input resistance (ph-n)
Power consumption per phase
AC current input
Only for connection to external current transformers
Input current I
Surge withstand capability
Power consumption per phase
Measuring accuracy
Measured variable
Voltage
Current
Power
Frequency
Power factor
Active energy
Reactive energy
When measuring on external current transformers or voltage transformers, the accuracy of
the measurement depends on the quality of the transformer.
Digital input
Number
Input voltage
Input current
158
I
Rated value
Maximum input voltage
Switching threshold for signal "1" > 11 V DC
For signal "1"
V
to 400 V (V
), max. 347 V for UL
I
ph-n
(not for device with extra-low voltage power
supply)
V
to 690 V (V
), max. 600 V for UL
I
ph-n
(not for device with extra-low voltage power
supply)
Higher voltages only if using voltage transformers
1.05 Mohms
220 mW
3~ x AC / 1 A (+ 20%, max. 300 V) or
3~ x AC / 5 A (+ 20%, max. 300 V)
100 A for 1 s
4 mVA at 1 A
115 mVA at 5 A
Error limits
± 0,3 %
± 0,2 %
± 0,5 %
± 0,05 %
± 0,5 %
Class 0.5S in accordance with IEC 62053-
22:2003-01
Class 2 in accordance with IEC 62053-23:2003-
01
1 input
24 V DC
30 V DC
typ. 7 mA
CAT III
CAT III
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04