Table 3-1 Device Versions - Siemens SENTRON PAC3200 Manual

Power monitoring device
Hide thumbs Also See for SENTRON PAC3200:
Table of Contents

Advertisement

Description
3.1 Features
Device versions
The device is available in the following versions:
Table 3-1
Device versions
SENTRON PAC3200 Power Monitoring Device
Order No.
7KM2112-0BA00-2AA0
7KM2112-0BA00-3AA0
7KM2111-1BA00-3AA0
Measurement
● Derivation of more than 50 measured variables from the basic measured variables with
● With the multi-range power supply, the SENTRON PAC3200 can be connected direct to
● With the extra-low voltage power supply, the SENTRON PAC3200 can be connected
● For current transformers x/1 A and x/5 A. Conversion ratio and current direction
● Can be used in 2-, 3- and 4-wire systems. Suitable for TN, TT and IT systems.
● High measuring accuracy: 0.5% of the measured value for energy.
Counters and power demand
● A total of 10 energy counters capture active energy, reactive energy, apparent energy for
● Calculation and storage of the last demand period mean value for active power and
● Configurable universal counter for counting limit violations and status changes at the
● Working hours counter for monitoring the runtime of a connected load.
20
Description
SENTRON PAC3200 with multi-range power supply with ring lug terminals
SENTRON PAC3200 with multi-range power supply with screw terminals
SENTRON PAC3200 with extra-low voltage power supply with screw terminals
maximum and minimum values (slave pointer function), as well as mean values for
phase-to-neutral voltages, phase-to-phase voltages and currents. The minimum and
maximum values are indicated in addition to the mean values.
690 V (max. 600 V for UL) industrial systems (measuring category III, pollution degree 2).
Higher voltages using voltage transformers.
direct to systems up to 500 V.
programmable.
off-peak and on-peak, import and export.
reactive power for simple generation of load profiles using software. Programmable
demand period from 1 to 60 mins.
digital input or output, or for indicating the active power or reactive power of a connected
pulse encoder, e.g. S0 interface.
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04