Overview Of Field Settings - Daikin FTX-N Series Service Manual

Inverter pair: wall mounted type, floor standing type, duct connected type.
Hide thumbs Also See for FTX-N Series:
Table of Contents

Advertisement

Field Settings for FDMQ Series
5.2

Overview of Field Settings

First
Mode
Code
No.
01
No.
Approx.
2,500 hrs.
0
10
Approx.
(20)
200 hrs.
3
Display
11
7
OFF
(21)
Note(s)
 The Second Code No. is factory set to "01".
 Do not use any settings not listed in the table.
 For group control with a wireless remote controller, initial settings for all the indoor units of the
External Static
12 class
Pressure Settings
Mode
No.
(23)
213
Second Code No.
02
Approx.
1,250 hrs.
Approx.
100 hrs.
No display
Air volume
adjustment
completion
group are equal.
For group control, refer to the installation manual attached to the indoor unit for group control.
First
Code
Second Code No.
No.
03
04
05 
06
07
08
13
6
09
10
11
12
13
14
15
03
Filter cleaning sign interval (used to
change filter cleaning display
interval according to filter
contamination)
Filter cleaning sign (used to set filter cleaning display
ON/OFF)
Air volume
Air volume adjustment
adjustment start
External static pressure
30 Pa
40 Pa
50 Pa 
60 Pa
70 Pa
80 Pa
90 Pa
100 Pa
110 Pa
120 Pa
130 Pa
140 Pa
150 Pa
Factory Setting
SiUS091601EA
Description of setting
Longlife filter
Standard
filter
Factory Setting
Part 7 Trial Operation and Field Settings

Advertisement

Table of Contents
loading

Table of Contents