Outdoor Unit; Rxl09Qmvju - Daikin FTX-N Series Service Manual

Inverter pair: wall mounted type, floor standing type, duct connected type.
Hide thumbs Also See for FTX-N Series:
Table of Contents

Advertisement

SiUS091601EA

4. Outdoor Unit

4.1

RXL09QMVJU

Main PCB (PCB1)
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
13)
14)
Part 3 Printed Circuit Board Connector Wiring Diagram
S20
Connector for electronic expansion valve coil
S30
Connector for compressor
S40
Connector for overload protector
S71
Connector for DC fan motor
S80
Connector for four way valve coil
S90
Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
HL1, HN1, S
Connector for terminal block
E1, E2
Terminal for ground wire
HR1, HR2
Connector for reactor
FU1, FU2
Fuse (3.15 A, 250 V)
FU3
Fuse (20 A, 250 V)
J6
Jumper for facility setting
Refer to page 217 for details.