Daikin FTX-N Series Service Manual page 79

Inverter pair: wall mounted type, floor standing type, duct connected type.
Hide thumbs Also See for FTX-N Series:
Table of Contents

Advertisement

SiUS091601EA
If Float Switch is OFF with Thermostat ON in Cooling Operation
 When the float switch stays OFF for 5 sec., the thermostat turns OFF.
 After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
1. If the float switch turns ON again during the residual operation of the drain pump, cooling
2. If the float switch remains OFF even after the residual operation of the drain pump has
3. The drain pump turns OFF once residual operation has ended, then turns ON again after
4. After A3 is determined and the unit comes to an abnormal stop, the thermostat will
If Float Switch is OFF with Thermostat OFF in Cooling Operation
 When the float switch stays OFF for 5 sec., the drain pump turns ON.
 If the float switch remains OFF even after the residual operation of the drain pump has ended,
 The drain pump turns OFF once residual operation has ended, then turns ON again after 5
Part 4 Functions and Control
OFF
Float switch
ON
ON
Thermostat
(running)
OFF
ON
Error display
OFF
ON
Drain pump
OFF
operation also turns on again (thermostat ON).
ended, the error code A3 is determined.
5 seconds.
remain OFF even if the float switch turns ON again.
OFF
Float switch
ON
ON
Thermostat
(running)
OFF
ON
Error display
OFF
ON
Drain pump
OFF
the error code A3 is determined.
seconds.
∗1
5 sec.
5 sec.
5 min. 5 sec.
A3
5 sec.
5 min. 5 sec.
5 min.
Functions for FDMQ Series
∗2
∗4
∗3
A3
5 min.
5 sec. 5 min. 5 sec.
5 sec.
5 min.
(R24611)
(R24610)
74