3.2
Installing the built-in unit
3.2.1
Notes on installation
Before installing the device, please ensure that the installation location complies with the
following:
NOTICE
Use according to IEC 61010-2-201 requires an appropriate enclosure
The rear of the built-in device is classified as "Open Equipment" according to
IEC 61010-2-201 for use in industrial control equipment.
The installation of the device in an enclosure conforming to IEC 61010-2-201 is a
mandatory requirement for approval and operation in accordance with IEC 61010-2-201.
● Position the device so that it is not exposed to direct sunlight.
● Position the device so that it is easily accessible for the operator.
● Choose a suitable installation height.
● Ensure that the air vents of the device are not covered as a result of installation. Note the
permitted mounting positions.
3.2.2
Positions of the mounting clips
You fasten the built-in devices with 12 mounting clips from the accessory pack, which are
also available as accessories.
See also section "Accessories (Page 25)".
IFP V2, IFP V2 PRO
Operating Instructions, 08/2019, A5E46641410-AA
Installing and connecting the device
3.2 Installing the built-in unit
45