Safety information

2.2 Notes about usage

2.2
Notes about usage
NOTICE
Device approved for indoor use only
The device may be damaged if operated outdoors.
Operate the device indoors only ("Indoor use only").
Note
Operate the device only in a normal atmospheric environment
The technical characteristics of the device described in the operating instructions are
guaranteed if you operate the device in normal ambient air conditions with usual air
composition.
Note
The device is intended for operation in an SELV/PELV circuit according to
IEC/EN 61010-2-201 in a dry environment, which means for the various device types:
• Built-in devices: dry environment on the rear of the device
• PRO devices: dry environment inside the housing
• Transceiver Unit: dry environment all around
Additional information is available in the section "Operating Conditions (Page 92)".
Industrial applications
The device is designed for industrial use. It conforms to the following standards:
● Requirements for interference emissions EN 61000-6-4
● Requirements for interference immunity EN 61000-6-2
Use in mixed-use zone
Under certain circumstances you can use the device in a mixed-use zone. A mixed-use zone
is used for housing and commercial operations that do not have a significant impact on
residents.
When you use the device in a mixed-use zone, you must ensure that the limits of the generic
standard EN 61000-6-3 regarding emission of radio frequency interference are observed.
Suitable measures for achieving these limits for use in a mixed-use zone include:
● Installation of the device in grounded control cabinets
● Use of filters in electrical supply lines
Individual acceptance is required.