Temperature Converter HiC2081, HiD2081, HiD2082
Factory settings
10
Factory settings
The device is supplied with preset factory parameters. The following table lists all parameters.
Parameter
Supply Frequency
Input
Sensor
Connection Mode
Unit
Cold Junction
Compensation
Ext. Ref. Temp.
Lead Resistance
Sensor Breakage
Sensor Short Circuit
Rate
Firmware Version
Input Extra
Redundancy
Maximum Deviation
Output
Assigned Input
Characteristic
Start Value
End Value
Error Indication
Output Invert
Output Type
50 - EN
Factory settings
50 Hz
1
2 (only HiD2082)
Pt100
3-wire
°C
Internal (H-CJC-*)
Internal (H-CJC-*)
25 °C
0.00
Active
Active
Standard
Standard
Version 1.35
Version 1.35
Deactivated
1 °C
1
2 (only HiD2082)
1
2 (only HiD2082)
4 ... 20 mA, NE 43
4 ... 20 mA, NE 43
0 °C
200 °C
Downscale
Downscale
Deactivated
Deactivated
Current Output
Current Output
1
Pt100
3-wire
°C
25 °C
0.00
Active
Active
1
0 °C
200 °C
Own settings
2 (only HiD2082)
2 (only HiD2082)