STEP 7.5 MODULE 9 FACTORY SERVICE OPERATIONS (
CALIBRATION
4;-'
The controller is fully calibrated from the
factory. Recalibration is recommended every two
<H
years by qualified technicians using appropriate
equipment. Calibration may be performed by
using the front panel or with the TP16KIT. The front panel
method is explained below. (Refer to the TP16KIT bulletin for
calibration instructions using TP16KIT cable and software.)
Calibration may be aborted by disconnecting power to the
controller before exiting Factory Service Module
case, the existing calibration settings remain in effect.
Note: Allow the controller to warm up for 30 minutes minimum
and follow the manufacturer's warm-up recommendations for
the calibration source or measuring device.
Millivolt Calibration (T16)
Millivolt calibration requires a precision voltage source with an
accuracy of 0.03% (or better) connected to terminals 8 (comm.)
and 9 (+). When calibrating the input, the millivolt calibration must
be performed first, then the Cold Junction or RTD Resistance.
PROMPT
APPLY
FRONT PANEL ACTION
[CodE]
Press $ until
[CAL]
Press # for
[StP1]
After 5 seconds (minimum), press ".
0.0 mV
[StP2]
After 5 seconds (minimum), press ".
14.0 mV
[StP3]
After 5 seconds (minimum), press ".
28.0 mV
[StP4]
After 5 seconds (minimum), press ".
42.0 mV
[StP5]
After 5 seconds (minimum), press ".
56.0 mV
Cold Junction (T16)
Cold Junction calibration requires a thermocouple of known
accuracy of types T, E, J, K, C or N (connected to terminals 8 and
9) and a calibrated external reference thermocouple probe
measuring in °C with resolution to tenths. The two probes should
be brought in contact with each other or in some way held at the
same temperature. They should be shielded from air movement
and allowed sufficient time to equalize in temperature. (As an
alternative, the T16 thermocouple may be placed in a calibration
bath of known temperature.) If performing the millivolt calibration
prior, verify that the correct input type is configured in Input
Module
0.1(
before performing the following procedure. (After
the millivolt calibration the controller will default to type J.) If using
RTD only, the cold junction calibration need not be performed.
PROMPT
COMPARE
[CodE]
Press $ until
[CAL]
Press ".
[CJC]
Press # for
Press # or $ to adjust the
Top display to
bottom display until the top
external
process display matches the
reference
external reference then press ".
RTD Resistance (T16)
an accuracy of 0.1 Ω (or better). Connect a jumper between
terminals 9 and 10 with a 0 ohm jumper between 9 and 8 at
and the 277.0 ohm resistor between 9 and 8 at
thermocouple only, the RTD calibration need not be performed.
PROMPT
[CodE]
[CAL]
[CJC]
[rtd]
[StP1]
[StP2]
Input Calibration (P16)
accuracy of 0.03% (or better) that is capable of generating 10.0
V connected to terminals 8 (COMM) and 9 (+10V) and 20.00 mA
5./)
. In this
connected to terminals 8 (COMM) and 10 (20mA). The current
calibration can be skipped by pressing " at the not applicable
prompts if using the controller for process voltage only.
PROMPT
[CodE]
[CAL]
[StP1]
[StP2]
[StP3]
[StP4]
, press ".
<H
[StP5]
, press ".
?')
[StPA]
[StPb]
Analog Output Calibration (T16 and P16)
calibrated. Connect an external meter with an accuracy of 0.05%
(or better) that is capable of measuring 10.00 V or 20.00 mA to
terminals 6 (+V/I) and 7 (-V/I). The voltage or current calibration
that is not being used must be skipped by pressing " until End
appears.
PROMPT
[CodE]
[CAL]
[CJC]
[rtd]
[ANCL]
[C 0v]
FRONT PANEL ACTION
C 10v
, press ".
<H
C 0c]
, press ".
?')
C 20c
20
RTD calibration requires a precision 277.0 ohm resistor with
APPLY
FRONT PANEL ACTION
Press $ until
Press ".
Press ".
Press # for
After 5 seconds (minimum), press ".
0.0 ohm
After 5 seconds (minimum), press ".
277.0 ohm
Process calibration requires a precision signal source with an
APPLY
FRONT PANEL ACTION
Press $ until
Press # for
After 5 seconds (minimum), press ".
0.0 V
After 5 seconds (minimum), press ".
2.5 V
After 5 seconds (minimum), press ".
5.0 V
After 5 seconds (minimum), press ".
7.5 V
After 5 seconds (minimum), press ".
10.0 V
After 5 seconds (minimum), press ".
0.0 mA
After 5 seconds (minimum), press ".
20.0 mA
Set the controller Analog jumpers to the output type being
EXTERNAL
FRONT PANEL ACTION
METER
Press $ until
Press ".
Press ". (T16 only)
Press ". (T16 only)
Press # for
Press # or $ until external meter
0.00 V
matches listing, press ".
Press # or $ until external meter
10.00 V
matches listing, press ".
Press # or $ until external meter
0.00 mA
matches listing, press ".
Press # or $ until external meter
20.00 mA
matches listing, press ".
),&0
),&8
. If using
, press ".
<H
, press ".
?')
, press ".
<H
, press ".
?')
, press ".
<H
, press ".
?')
)
5./)