DISPLAY VALUE SCALING POINT 2
-)&8
.555
to
5555
0667 6
Enter the second coordinate Display Value by using the arrow
keys.
INPUT VALUE SCALING POINT 2
1(&8
67 6 6
to
867 6 6
mA
to
67 6 6
067 6 6
V
867 6 6
For Key-in Method, enter the second coordinate Input Value
by using the arrow keys. To allow the P16 to "learn" the signal,
use the Applied Method. For Applied Method, press !. The °
annunciator is turned on to indicate the applied method. Adjust
the applied signal level externally until the appropriate value
. Using either method, press " to store the
appears under
1(&8
value for
1(&8
. (The controller can be toggled back to the Key-in
Method by pressing ! before ".)
SETPOINT LOW LIMIT
)&#"
.555
to
5555
67 6
The controller has a programmable low setpoint limit value to
restrict the setting range of the setpoint. Set the limit so that the
setpoint value cannot be set below the safe operating area of the
process.
SETPOINT HIGH LIMIT
)&*1
.555
to
5555
5557 5
The controller has a programmable high setpoint limit value to
restrict the setting range of the setpoint. Set the limit so that the
setpoint value cannot be set above the safe operating area of the
process.
USER INPUT FUNCTION (OPTIONAL)
12&,
&#"4
SELECTION
FUNCTION
NONE
No Function
PLOC
Program Lock
ILOC
Integral Action Lock
trnF
Auto/Manual Select
The controller performs the selected User Input function (User
Input available only on models with alarms), when the User
terminal 1 is connected (pulled low) to Common terminal 8.
No Function: No function is performed.
Program Lock: The Configuration Loop is locked, as long as
activated (maintained action).
Integral Action Lock: The integral action of the PID
computation is disabled (frozen), as long as activated
(maintained action).
Auto/Manual Select: This function selects (maintained action)
Automatic (open) or Manual Control (activated).
Setpoint 1 or 2 Select: This function selects (maintained action)
Setpoint 1(open) or Setpoint 2 (activated) as the active
setpoint.
Setpoint Ramp Disable: The setpoint ramping feature is
disabled, as long as activated (maintained action). Any time
the user input is activated with a ramp in process, ramping is
aborted.
Reset Alarms: Active alarms are reset, as long as activated
(maintained action). Active alarms are reset until the alarm
condition is cleared and triggered again (momentary action).
F1 KEY FUNCTION
/012
("('
SELECTION
FUNCTION
NONE
No Function
trnF
Auto/Manual Select
SPt
Setpoint 1 or 2 Select
The controller performs the selected F1 key function, when !
is pressed while in the Display Loop. In any other loop or module
location, pressing ! will perform an escape to the Display Loop.
No Function: No function is performed.
Auto/Manual Select: This function toggles (momentary action)
the controller between Automatic and Manual Control.
Setpoint 1 or 2 Selection: This function toggles (momentary
action) the controller between Setpoint 1 and Setpoint 2.
Reset Alarms: This function can be used to reset one or both of
the alarms when activated (momentary action). The alarm will
remain reset until the alarm condition is cleared and triggered
again.
14
SELECTION
FUNCTION
SPt
Setpoint 1 or 2 Select
SPrP
Setpoint Ramp Disable
ALrS
Reset Both Alarms
SELECTION
FUNCTION
A1rS
Reset Alarm 1
A2rS
Reset Alarm 2
ALrS
Reset Both Alarms