Engine Break-In Requirements; Resetting The Maintenance Alarms - Generac Power Systems Magnum Series Operating Manual

Diesel generator with powerzone controller
Table of Contents

Advertisement

Replace Air Cleaner Elements
Replace Alternator and Fan Belts
Check Fuses
Add Coolant
Check Electrical Wiring and Connections
*
Replace primary air cleaner when dust valve restriction indicator gauge shows a vacuum of 25 in. H
**
Change the oil and oil filter after the first 100 hours, then every 500 hours. If not using John Deere Plus 50 II
engine oil, the interval must be decreased to every 250 hours.

ENGINE BREAK-IN REQUIREMENTS

Note: During the first 20 hours of operation, avoid long periods of no load or sustained maximum load operation. If
the generator is to run for longer than five minutes without a load, shut the generator down.
John Deere engines are supplied with engine break-in oil from the factory. Extra care during the first 100 hours of
engine operation will result in better performance and longer engine life. DO NOT exceed 100 hours of operation
with the break-in oil. Operate the engine at heavy loads (60-90% of maximum) as much as possible. If the engine
has spent significant time at idle, constant speed(s), and/or light load, or if makeup oil is required, a longer break in
period may be needed. Refer to the engine operator's manual for a full description of necessary procedures on the
addition of break-in oil and extension of the break-in period. For more information on regular maintenance intervals,
refer to
Basic Maintenance Schedule - John Deere

RESETTING THE MAINTENANCE ALARMS

The Power Zone™ controller will display a warning message when the unit is due for maintenance or service. The
maintenance or service interval is set at 250, 500 and 3000 hours of engine running time. Once the unit has been
serviced, the appropriate maintenance alarm reminder needs to be reset. The following procedure demonstrates
how to reset the maintenance alarms:
1. With the unit shut down, move the control power switch to ON (I). After initialization, the controller will toggle
automatically to the Home screen.
Press any directional arrow (▲, ►, ▼, ◄) to enter the maintenance screens.
2.
Press the Enter () button and the Engine Stop/Reset (O) button simultaneously. The next screen will dis-
3.
play the Configuration menu.
Press  to move the cursor (blue highlighted text) down to the "Maintenance" group.
4.
Press ► to access the sections. Press  to highlight the "Maintenance" section.
5.
Press ► to access the parameters and highlight the maintenance alarm that needs to be reset.
6.
Press the Enter () button to select the editable parameters. The cursor will highlight "Not Reset" under the
7.
selected maintenance alarm. Press  to highlight "Reset".
Press the Enter () button to reset the selected maintenance alarm.
8.
To perform additional maintenance alarm resets, repeat steps 6 - 8.
9.
Note: If the selected maintenance alarm does not need to be reset, press the  button to highlight "Not Reset" and
press the Enter () button return to the parameters section.
33722 D
Item
MMG130DI4/175DI4/205DI4 Operating Manual
250
Daily
Hrs.
Engine.
Maintenance
500
3000
Hrs./12
Hrs./ 36
Required
Months
Months
2
As
O.
39

Advertisement