Generator Screen; Voltage Adjust Screen - Generac Power Systems Magnum Series Operating Manual

Diesel generator with powerzone controller
Table of Contents

Advertisement

General Information
Battery: Displays the engine battery voltage. Current battery voltage is displayed directly below the gauge
at all times. The gauge displays battery voltage between 0-50V. A normal reading is 12-14V on 12 volt
systems and 24-26V on 24 volt systems (with the engine running).

Generator Screen

The Generator screen displays the average voltage frequency, volts and amps from the generator, as well as line-
to-line voltage, and individual line-to-neutral voltage, amperage and power (kW). This screen also displays the
generator winding configuration set by the voltage selector switch in the lower right corner.
Note: When loading the generator, it is important to observe the amperage to determine the load balance on each
line of the generator. Minor load unbalances, usually ten percent or less, will not cause problems. Every effort should
be made to distribute the load equally between all lines.
Freq: Displays the output frequency in Hertz (Hz). Normal operating frequency is 60 Hz.
Volts: Displays the nominal voltage in Volts (V).
Amps: Displays the AC output amperage produced by the generator in Amps (A).
Additional information can be found on the electric power table at the bottom-left side of the screen. This provides
an overview of all three lines and average voltage and amperage readouts.

Voltage Adjust Screen

The Voltage Adjust screen displays the line-to-neutral and line-to-line voltage averages. The operator can electron-
ically adjust the voltage within limits to prevent under-voltage or over-voltage conditions using the on-screen
instructions. This feature replaces a traditional potentiometer. See
16
Manual Mode
30
40
20
50
88
10
60
GEN
Freq
0
70
+ -
V
Volt
Volt
Amp
0
0
L1-L2
L1
0
0
25
L2-L3
L2
0
0
50
L3-L1
L3
IE
Figure 2-9. Generator Screen
MMG130DI4/175DI4/205DI4 Operating Manual
175
25
263
13
Volt
Amp
0
350
0
50
Parallel Low Zig-Zag
kW
0
0.0
0.0
0.0
N
L1 (U)
0
L2 (W)
00395
Fine Voltage Adjustment
38
for more information.
33722 D

Advertisement

Table of Contents
loading

This manual is also suitable for:

Magnum mmg130di4Magnum mmg175di4Magnum mmg205di4

Table of Contents