Input Trigger Types: Triggering of each zone input can be programmed to cause an alarm under one of the
following conditions:
 (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
 (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
 (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
Inverted Trigger: Zones can be programmed for inverted trigger, where the alarm and normal states of the zones
are inverted; this can serve a fail-safe supervisory purpose for certain installations.
Restore and Delayed Reports: Zone inputs can be programmed for restore reporting, and for delayed reporting
(allowing time for the user to abort false alarms).
UL: Zone restoral must be enabled.
Report Only if Armed option: To help eliminate redundant reports, zone alarms can be restricted to report only if
a conditional zone is triggered (armed). If this feature is desired, the conditional zone is automatically used as the
"arming" zone. Connect the appropriate control panel trigger to the conditional (arming) zone. The trigger must be
programmed as necessary in the control panel.
The conditional (arming) zone on the module is a different dedicated zone for each programming mode, as follows:
IMPORTANT: If any zone (zones 1-6 in zone trigger mode, zones 1-3 in 4204 mode, zones 1-7 in 2-4204 mode) is set
for Report Only if Armed, the conditional (arming) zone becomes unavailable for reporting (as it is reserved for the
"arming" trigger connection).
Trip Inputs 1or2
24
w/Bell Out (N)_
Telco Zone
25
(0)_
4204/
ZONE
ENTRY
2-4204
TRIG.
Mode
Zone Trigger
4204
2-4204
Section 3: Programming the GSMHS
OPTIONS
Conditional (Arming) Zone
7
4
8
[Y], [N]
Use if the zone 1 connection to the control's
bell output causes a bell fault on the control
panel.
NOTE: If used, EOLR trigger type is not
available for zones 1 and 3.
UL: Use of the bell output is not supported.
See "Important Information Regarding Zone
Zone Trig:
Input Options" on previous page.
[3-7]
Enter the zone number to be used for Telco
4204: [1-4]
line fault reports. This zone assignment must
be unique from the open/close zone selected in
2-4204:
Prompt 26.
[1-8]
Zone Trigger Mode: If any zone is
[0] = not
programmed for "report only if armed,"
used
zone 7 cannot be used.
4204 Mode: If any zone is programmed for
"report only if armed," zone 4 cannot be
used as a Telco zone.
2-4204 Mode: If any zone is programmed for
"report only if armed," or if tamper
reporting is enabled, zone 8 cannot be used.
NOTE: Connect the Telco line fault output (or
relay output programmed for "Telco line
fault") to the Telco zone.
DESCRIPTION