PROMPTS
12
Primary Sub ID
(????)
Device Address
13
(12)_
14
Direct Wire
Y/N
(N)_
15
Keypad Address
(28)_
16
Supervision
(US Hi Line
Sec S)_
Old Alarm Time
17
10 Minutes_
4204/
ZONE
ENTRY
2-4204
TRIG.
Section 3: Programming the GSMHS
OPTIONS
[0001-
Enter the 4-digit subscriber account number,
9999]
0001-9999 (decimal).
The GSMHS communicates with the control
[01-15]
panel as a 4204 relay module. Enter the
appropriate address. For VISTA-10P and
FA130CP Series control panels, this must be
address 12. For other controls, see the control
panel's Installation and Setup Guide.
NOTES:
1. The 4204 protocol limits address range to
01-15. If using 2-4204 mode, the GSMHS
assigns the second 4204 to the next higher
device address (e.g., if entering address 12
for the first 4204, then address 13 is
automatically assigned to the second 4204
module). Program the control panel
accordingly.
2. The device address(es) must be unique from
the "Keypad Address" entered in Prompt 15
and any other address used on the control
panel.
Applies only to
[Y], [N]
FBP Series controls.
If [N], skip to Prompt 16: "Supervision."
This address must be programmed if using
[01-30]
Direct Wire downloading.
NOTES:
1. This address must be programmed as an
alpha keypad in the control panel (Device
Programming Mode).
2. This address must be unique from the
"Device Address" entered in Prompt 13, and
cannot equal that device address plus 1
(one) if using 2-4204 mode.
The AlarmNet network must hear at least one
US Hi Line
message from the device during the supervi-
Sec S
sion interval; otherwise, AlarmNet notifies the
central station that a communication failure
has occurred. This interval satisfies the 200
second single path comm. fail requirement.
This interval cannot be changed.
 10 Min
Sets how long an undeliverable alarm is
 15 Min
retried for delivery to the central station. If
the message is not validated, it is retried until
 30 Min
the old alarm time is reached or the message is
 1 Hr
validated.
 2 Hrs
 4 Hrs
Press the [space] key to scroll through choices.
 8 Hrs
 12 Hrs
UL: Must be set to 10 minutes.
 24 Hrs
DESCRIPTION