TROUBLESHOOTING

PROBLEM
Indicator LED is not illuminated.
Transmitter : During normal operation
Receiver
: Light interrupted
"ALARM" indicator LED is not
illuminated even if the beam is
blocked.
Blocking the beam, and
illuminates "ALARM" indicator LED
but does not active the alarm.
Alarm is activated even if the light
is not blocked.
Frost, snow or heavy rain causes
false alarm.
Improper output
9

SPECIFICATIONS

< SL-200QN, SL-350QN, SL-650QN >
Model
Maximum detection range
Maximum arrival distance
Detection method
Interruption time
Power source
Current draw
Alarm output
Output
Alarm period
Tamper output
Operating temperature
Operating humidity
Alignment angle
Dimension
Weight
International protection
< HU-3 (Option) >
Model
Power input
Current draw
Thermo switch
Operating temperature
Weight
Packages
POSSIBLE CAUSE
Inappropriate power voltage
Inappropriate wiring distance or wire diameter
ReÀection of the Àoor or wall
Beam has not been blocked.
Signal line short-circuited
Alarm contact welded
Interruption time is too short.
Surface of Transmitter/Receiver cover soiled.
Optical alignment was not performed properly.
Optical alignment is not optimazed.
The wiring is incorrected.
SL-200QN
60 m/200ft
600 m/2000ft
38 mA
(Transmitter: 8 mA Receiver: 30 mA)
N.C. (contact output): 30 VDC, 0.1 A Opens when cover removed.
H
2400 g (84.7oz) (Total weight of Transmitter + Receiver, excluding accessories)
HU-3
24VAC/DC
420mA(max.) (Per 1 unit)
60°C (140°F)
-35°C - +60°C(-31°F - +140°F)
20g(0.7oz) (Heater(x2))
Heater(x2), Connector(x4), Waterproof agent
Check the voltage and make sure that it is
between 10.5 and 30 VDC.
See "2-5 WIRING DISTANCE BETWEEN POWER
SUPPLY AND DETECTOR" on page 4,check the
wiring distance.
See"4-1 OPTICAL ALIGNMENT" on Page 8 and
make realignment.
Block all four beams at same time.
Check the wiring.
Repair is required. Contact the distributor or us.
See "3-1 BEAM INTERRUPTION ADJUSTMENT"
on page 8, set an appropriate interruption time.
Clean the cover (wipe the cover with a soft cloth
dampened with water od diluted neutral detergent).
See"4-1 OPTICAL ALIGNMENT" on Page 8 and
make realignment.
See"4-1 OPTICAL ALIGNMENT" on Page 8 and
make realignment.
Make correct wiring.
SL-350QN
100 m/350 ft
1000 m/3500 ft
Quad infrared beam interruption detection
Variable between 50/100/250/500 ms
(4 steps)
10.5 - 30 VDC
39 mA
(Transmitter: 9 mA Receiver: 30 mA)
Form C relay: 30 VDC, 0.2 A
2 sec (±1) (Nominal)
-25°C - +60°C (-13°F - 140°F)
95 % (max.)
±90° Horizontal, ±10° Vertical
W
D mm (inch): 448 (17.6) x 79 (3.1) x 96 (3.8)
IP65
NOTE
These units are designed to detect an intruder and
activate an alarm control panel. Being only a part of a
complete system, we cannot accept responsibility for
any damages or other consequences resulting from an
intrusion.
These products conform to the EMC Directive
2004/108/EC.
-11-
CORRECTIVE ACTION
SL-650QN
200 m/650 ft
2000 m/6500 ft
40 mA
(Transmitter: 10 mA Receiver: 30 mA)