Advertisement

Allocate a relay channel to control valve 2

In our example, the second temperature sensor must control relay channel 4 of the first relay module to steer the valve.
1. Set the second sensor module in anti-freeze mode by
pressing the push button on the front panel
repeatedly until all LEDs are off.
2. Set the MODE and TIME1 rotary switches for
channel 4 of the first relay module to '0' (instant
control).
3. Remember the address of this relay module to
reinstate it later on.
4. Set the address of the first relay module to 'C4'.
The 'MODE 4' LED flashes to indicate push button
learning mode (PBM).
Out1
Out2
Mode/
Mode/
Mode/
Mode/
ADDR.
Time2
Time2
Time2
ADDR.
Time2
0
0
0
Time1
Time1
Time1
0
0
0
Learn
CH1
CH2
Fx
:
OFF
x=CH1...4
Ex
: ON
:
:
9x :
Dx
TGL
Bx
TG1
ST1
Cx
:
PBM
Ax
:
TG2
8x
:
ST2
ON
Rx
Tx
Mode1
16
Out3
Out4
4 Channel relay module
Mode/
Time2
Time1
Mode/Time2
0
0
0:Moment
Start-stop
1:5s
Staircase
2:10s
Non-Retrigger
3:15s
Turn Off Delay
4:30s
Turn On Delay
5:1'
Trig Release
Time1
6:2'
Blink
0
0
7:5'
5'
8:10'
10'
9:15'
15'
A:30'
30'
CH3
CH4
B:1h
1h
C:2h
2h
VMB4RY
D:5h
5h
E:1day
1day
velleman
F:Toggle
Toggle
Mode2
Mode3
Mode4
VMB1TC Temperature controller manual – rev 5.0
5. Press and hold the lowest push button (HEAT) of the
second temperature sensor until the relay is
energised and the red LED on the sensor module
flashes.
6. Set the address of the first relay module back to its
original value.