Siemens SITRANS RD200 Operating Instructions Manual page 84

Communication and displays.
Hide thumbs Also See for SITRANS RD200:
Table of Contents

Advertisement

Register
Name
1
Number Address
(hex)
40102
101
Active
(0065)
Decimal
Point
40103
102
Current
and
(0066)
Voltage
decimal
points
40104
103
Adjust
(0067)
40105
104
Bypass
(0068)
40106
105
Cutoff
(0069)
40107
106
Filter
(006A)
84
Access
Limits
Units
or
Range
2
Read
1, 2,
None
Write
3, or 6
Read
0x00CV,
None
Write
where
C & V =
1, 2, 3, or
6.
Read
-199
°C or °F
Write
to
+199
Read
2
Percent
Write
to
of full
999
scale or
°F
Read
0
User
Write
to
Defined
9999
Read
0, 2
Unit-less
Write
to
199
Data
Function
Comments
Type
Code(s)
3
Integer
03,
6 = no decimal point. 1 to 3 =
number of digits to right of
06,
dp. Mirror of bits 6-4 of
16,
40101. Only process decimal
04
points can be written. Writing
a non-process dp returns
0xFFFF.
Word
03,
See "Decimal Point for
RD200" on page 96. If an out
06,
of range value is sent for
16,
either or both decimal points,
04
no change is made for that
value. Valid settings are
none, 1, 2, and 3 decimal
places.
Integer
03,
Actually represents -19.9 to
+19.9. Offset value is only
06,
applied to temperature in-
16,
puts. If Adjust is greater than
04
11°C and the temperature
units are switched to °F, it will
be set to 19.9 (lower than -
11, set to -19.9).
Integer
03,
Actually represents 0.2 to
99.9. If the input steps great-
06,
er than the bypass value, it
16,
will be displayed immediately,
04
with no filtering occurring.
The number represents per-
cent of full-scale for process
inputs and °F for temperature
inputs. No effect if filter = 0.
Integer
03,
Represents the cutoff value
without the decimal point.
06,
Valid only for process inputs.
16,
04
Integer
03,
Display filtering. 0 = no filter-
ing. New = old + ((new -
06,
old)/Filter)
16,
04
Operating Instructions, 05/2019, A5E47629414-AA