Setup
6.7 Advanced Features
Low-flow cutoff (cut F)
The low-flow cutoff feature allows the meter to be programmed so that the often unsteady
output from a differential pressure transmitter, at low flow rates, always displays zero on the
meter.
The cutoff value may be programmed from 0 to 9999. Below the cutoff value, the meter will
display zero. Programming the cutoff value to zero disables the cutoff.
1. Press and hold Right arrow
Features menu of the meter.
Press Up arrow
When the Select menu (
2. Press the Up
access the Cutoff menu.
3. Press Up arrow
to the next digit.
4. Press Ent/Ack
5. Press Menu
Display intensity (intY)
The Display Intensity function allows the selection of eight levels of intensity for various
lighting conditions.
1. Press and hold Right arrow
Features menu of the meter.
2. Press Up arrow
Select menu (SELc) is displayed, press Ent/Ack
3. Press Up arrow
4. Press Ent/Ack
5. Press Up arrow
intensity level is displayed, press Ent/Ack
6. Press Menu
48
and Menu
to scroll through the Advanced Features Menu options.
SELc
) is displayed, press Ent/Ack
arrow until the Cut F menu is displayed. Press Ent/Ack
to change the active digit and press Right arrow
to accept display setting.
to exit at any time.
and Menu
to scroll through the Advanced Features Menu options. When the
until Intensity menu (
to access the intensity setting.
to scroll through the eight intensity levels. When the desired
to exit at any time.
for three seconds to access Advanced
to access the menu.
for three seconds to access Advanced
to access the menu.
inty
) is displayed.
to accept the setting.
Operating Instructions, 05/2019, A5E47629414-AA
to
to advance
SITRANS RD200