PENSOTTI PCC 34-H Instruction Manual

Condensing direct vent gas boiler
Hide thumbs Also See for PCC 34-H:

Advertisement

Instruction Manual
Installer: Affix these instructions adjacent to the boiler
Homeowner: Retain these instructions for future reference
PCC 34-H
Condensing Direct Vent Gas Boiler
116,000 BTU INPUT
WARNING
If the information in these instructions is not followed exactly, a fire or explosion may
result, causing property damage, personal injury or death.
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or
-
any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance
• Do not touch any electrical switch; do not use any phone in your building
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
•If you cannot reach your gas supplier, call the fire department
-Installation and service be performed by a qualified installer, service agency or the gas
supplier.
-Use of a properly calibrated electronic combustion analyzer MUST be used to install and/or
service this appliance.
Approved in accordance with:
ANSI Z21.13b-2010 / CSA 4.9b (2010) Low Pressure Boiler
Manufactured/Distributed by: Granby Furnaces Inc.
12118 Hwy 209, Parrsboro, NS, Canada

Advertisement

Table of Contents
loading

Summary of Contents for PENSOTTI PCC 34-H

  • Page 1 Instruction Manual Installer: Affix these instructions adjacent to the boiler Homeowner: Retain these instructions for future reference PCC 34-H Condensing Direct Vent Gas Boiler 116,000 BTU INPUT WARNING If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury or death.
  • Page 2: Table Of Contents

    1. General information Pages 1.1 General warnings 1.2 Product conformity 2. Technical characteristics 2.1 Technical data 2.2 Dimensions 2.3 Internal parts of the boiler 2.4 Water circuit 2.5 Circulation pump head/flow graph 2.6 Printed circuit board – Technical characteristics 2.7 Control panel 3.
  • Page 3 Pages 6. Maintenance (authorized personnel) 6.1 General warnings 6.2 Maintenance 6.3 Boiler inspection 6.4 Accessing the boiler 6.5 Flushing out the primary side 6.6 Draining the central heating and domestic hot water system 6.7 Maintenance operations 6.8 Wiring diagrams 6.9 Troubleshooting 6.10 Diagnostics 6.11 Parts list 6.12 Sequence of Operations...
  • Page 4: General Information

    The appliance should be located in an area where leakage within the unit or at its connections will not result in damage to the area adjacent to the appliance or to lower floors of the structure. PENSOTTI will not be responsible for any damage resulting from leaking if adequate drainage is not provided. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.
  • Page 5 Check the Rating Plate PENSOTTI units come from the factory configured for use with natural gas. Prior to installation, check the rating plate of the boiler to ensure the unit matches gas type, gas pressure, water pressure and electrical supply. If the unit does not match the requirements, do not install.
  • Page 6 GENERAL INFORMATION The “operating instructions” chapter of this manual must be read carefully as it provides information on the operation and the operating limits of the appliance. After the removal of all the packaging, check that the appliance has not been damaged. In case of doubt, do not attempt to use the product but refer to the supplier.
  • Page 7 Many jurisdictions require the installation of carbon monoxide detectors in building where a side wall vented fuel burning appliance is installed. Installers must abide by local code requirements regarding the installation of CO detectors. The use of a certified carbon monoxide detector is recommended but not required by PENSOTTI. “In the State of Massachusetts only”...
  • Page 8 GENERAL INFORMATION...
  • Page 9 GENERAL Information...
  • Page 10 GENERAL Information...
  • Page 11 GENERAL Information...
  • Page 12: Product Conformity

    GENERAL INFORMATION 1.2 Product conformity All Granby/Pensotti LLC boilers are ETL certified and possess technical and functional characteristics that comply with the following standards: Gas fired Low Pressure Hot Water Boiler: American National Standard/CSA Standard for Gas Fired Low Pressure Steam and Hot W ater Boiler .
  • Page 13: Technical Characteristics

    TECHNICAL CHARACTERISTCS 2. TECHNICAL CHARACTERISTICS 2.1 Technical data Model PCC 34-H CE Certification n° 0694BN3485 Appliance Type B23p-B33-C13-C33-C43-C53-C63-C83-C93 Appliance Category II2H3B/P kW - BTU/hr 34 - 116013 Heat Input max kW - BTU/hr 10 - 34121 Heat Input min Heat Output max - 122/86°F kW - BTU/hr 36.2 - 123670...
  • Page 14: Dimensions

    TECHNICAL CHARACTERISTCS 2.2 Dimensions LEGEND HEATING RETURN Ø 3/4" HEATING FLOW Ø 3/4" Ø 1/2" Ø 1/2" COLD WATER INLET Ø 1/2" HOT WATER OUTLET CONDENSATE DRAIN Ø 0.98 in...
  • Page 15: Internal Parts Of The Boiler

    TECHNICAL CHARACTERISTCS 2.3 Internal parts of the boiler LEGEND PRIMARY CONDENSING HEAT EXCHANGER PREMIX BURNER UNIT (GAS MANIFOLD + BURNER) CONDENSATE DRAIN PIPE IONISATION ELECTRODE IGNITION ELECTRODE VENTURI IGNITION TRANSFORMER ELECTRONIC GAS VALVE " 10. RELIEF VALVE 3/4 11. AUTOMATIC AIR VENT VALVE 12.
  • Page 16: Water Circuit

    TECHNICAL CHARACTERISTCS 2.4 Water circuit LEGEND PRIMARY CONDENSING HEAT EXCHANGER PREMIX BURNER UNIT (GAS MANIFOLD+BURNER) CONDENSATE DRAIN PIPE IONISATION ELECTRODE IGNITION ELECTRODE VENTURI IGNITION TRANSFORMER ELECTRONIC GAS VALVE " 10. SAFETY VALVE 3/4 11. AUTOMATIC AIR VENT VALVE 12. HEATING SAFETY THERMOSTAT 13.
  • Page 17: Circulation Pump Head/Flow Graph

    TECHNICAL CHARACTERISTCS 2.5 Circulation pump head/flow graph Water flow [US gpm]...
  • Page 18: Control Panel

    TECHNICAL CHARACTERISTCS ® 2.6 DIGITECH printed circuit board – SM 20023 Technical characteristics Adjustments possible by service personnel only Standard (86-176° F) / reduced (77-104° F) central h e a t i n g temperature Water hammer prevention function Central Heating timer - (adjustable from 0 to 7,5 minutes) Central Heating pump overrun timer Domestic Hot W ater pump overrun timer Minimum Gas pressure setting...
  • Page 19 TECHNICAL CHARACTERISTCS LCD DISPLAY ICONS’ KEY 15. HEATING PARAMETER NUMBER INFORMATION PARAMETERS PROGRAMMING MODE ON SOLAR PCB CONNECTION INFORMATION / SOLAR PANEL TEMPERATURE DISPLAY (d6) SOLAR PUMP ON STORAGE CYLINDER LOW LEVEL TEMPERATURE VISUALIZATION (d7) / STORAGE CYLINDER HIGH LEVEL TEMPERATURE VISUALIZATION (d8) OUTDOOR TEMPERATURE SENSOR CONNECTED...
  • Page 20 TECHNICAL CHARACTERISTCS 2.8 INFO Menu display Press the ‘ ’ INFO Button to display the boiler data. Once pressed, the parameter number will appear on the left side of the display and the associated parameter value will appear on the centre of the display. Use ‘...
  • Page 21: Installation (Authorized Personnel)

    INSTALLATION INSTRUCTIONS 3. INSTALLATION (authorized personnel) 3.1 Reference standard Install in accordance with local building and electrical codes. Failure to install a gas appliance correctly and in accordance with the above norms could lead to prosecution. It is in the interest of the installer and safety that the codes are complied with. The manufacturer’s instructions form an integral part of the installation and should be left with the appliance but do not over ride in anyway statutory obligations.
  • Page 22: Unpacking

    Fig 1 STORAGE & HANDLING Please note that prior to installation the Pensotti North America boilers should be stored in the horizontal position with no more than three boilers to a stack;...
  • Page 23: Installing The Boiler

    INSTALLATION INSTRUCTIONS 3.3 Installing the boiler. The appliance must be installed exclusively on a vertical solid wall capable of supporting its weight. ■ The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse.
  • Page 24: Water Connections

    INSTALLATION INSTRUCTIONS 3.4 Water connections In order to safeguard the heat exchanger and circulation pump, especially in case of boiler replacement, it is recommended that the system is hot-flushed to remove any impurities (especially oil and grease) from the pipes and radiators.
  • Page 25: Domestic Hot Water Circuit / Hard Water Warning / Expansion Tank

    INSTALLATION INSTRUCTIONS 3.5 Domestic Hot Water Circuit ■ In order to prevent scaling and eventual damage to the D.H.W heat exchanger, the mains water supply must not have a hardness rating of more than 7 grains/gal (120 ppm). It is nevertheless advisable to check the properties of the water supply and install the appropriate treatment devices where necessary.
  • Page 26: Piping Diagram

    Dirt / Scale Separation Along with the application of our Fernox commissioning kit Pensotti highly recommends the installation of a dirt separator in the return piping of all Solenne Series boiler models. Follow the manufacturer’s instructions when installing these devices.
  • Page 27: Condensate Drain

    INSTALLATION INSTRUCTIONS 3.7 Condensate drain FAILURE INSTALL CONDENSATE Termination to an internal soil and vent pipe DISCHARGE PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE Boiler DUAL PURPOSE BOILER. condensate discharge pipe MUST NOT RISE at any point along its length.
  • Page 28: Gas Connection

    Until pressure testing of the main gas supply line is completed, ensure the gas line to the PENSOTTI Boiler is disconnected to avoid any damage to the boiler. The appliance and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 0.5 psi (3.5 kPa)..
  • Page 29 INSTALLATION INSTRUCTIONS Natural Gas Pipe Sizing Chart Size of Schd. 40 Black Iron Pipe in Inches Length of Pipe In Feet 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 1237 2259 1610 1335 1143 1041 Natural Gas flow is given in thousands of BTU/hr. - One cubic foot of natural gas = 1000 BTU Nominal pressure at the burner for Natural Gas is 3.5"...
  • Page 30: Electrical Connections

    130VAC Max or 95VAC Min. Damage caused by excessive voltage is not covered under warranty. DO NOT connect 220-240VAC and any other voltage to this PENSOTTI Boiler. This will damage the boiler and void the warranty. Do not disconnect the power supply when the unit is in normal operation.
  • Page 31 INSTALLATION INSTRUCTIONS Always check to make sure that the appliance has an efficient ground system. This requirement is only satisfied if it has been properly connected to an efficient ground system installed in accordance with the requirements of current safety standards and carried out by professionally qualified personnel. This basic safety measure must be checked, verified and carried out by professionally qualified personnel.
  • Page 32: Remote Control Connection

    INSTALLATION INSTRUCTIONS Remote control connection Connect the power supply to the terminal board inside the control panel as follows: a. Switch off the power supply at service switch or breaker. b. Remove the front case panel of the boiler. c. Slacken the screws and remove plate A (see fig. 1). d.
  • Page 33: Venting Connections

    All PENSOTTI b o i l e r s use a 3/ 5” c o nc e nt r ic v e nt or a 2 p ip es s ys t em t ha t u s es a 3”...
  • Page 34 INSTALLATION INSTRUCTIONS Venting Pictures & Illustrations...
  • Page 35 INSTALLATION INSTRUCTIONS Included With Each Combination Boiler Is A PAHVK Horizontal Kit...
  • Page 36 INSTALLATION INSTRUCTIONS 12” Clearance Suggested From The Top Of The Appliance To Ceiling 10” 7 ¾” Top of Appliance to Center Line Of Hole...
  • Page 37 INSTALLATION INSTRUCTIONS 3.11 2 Pipes Venting system Pictures & Illustrations The two pipes direct vent system can be installed in one of the following configurations. 1. Air Intake & Exhaust Pipes on an outside horizontal wall (intake and vent adjacent) 2.
  • Page 38 2” 50’ ( 25” air intake + 25’ exhaust) 3” 190’’ (95” air intake + 95’ exhaust) PCH 34B-H, PCC 34-H, PCI 34/20-H 2” 40’ (20’ air intake + 20’ exhaust) 3” 150’ ( 75” air intake + 75’ exhaust) PCH 50B-H 2”...
  • Page 39 INSTALLATION INSTRUCTIONS...
  • Page 40 INSTALLATION INSTRUCTIONS Follow all venting manufacturers’ guidelines for low-profile terminations.
  • Page 41 INSTALLATION INSTRUCTIONS The termination shall be located no less than 48” above or to the side of the exhaust for any other oil, gas or solid fuel appliance...
  • Page 42: Commissioning The Appliance (Authorized Personnel)

    INSTALLATION INSTRUCTIONS 4. COMMISSIONING THE APPLIANCE 4.1 General warnings The following operations must be carried out by professionally qualified personnel, registered in accordance with current legislation. Use of a properly calibrated electronic combustion analyzer MUST be used when installing, servicing or converting this Boiler from Natural Gas to LP or from LP to Natural Gas. The boiler leaves the factory pre-set and tested for burning either Natural Gas or LPG.
  • Page 43: Filling The System

    REGULATION INSTRUCTIONS 4.2 Filling the system Check the properties of the water supply and install the appropriate treatment devices if the mains water has a hardness rating more than 7 grains/gal. (120 ppm) in order to AIR VENT VALVE PLUG prevent scaling and eventual damage to the D.H.W heat exchanger.
  • Page 44: Flushing The System

    All systems must be thoroughly drained and flushed using additives – corrosion inhibitors and flushing agents/descalers. Pensotti requires the use of the supplied Fernox Commissioning Kit or individual containers of Fernox F3 or F5 cleaner and F1 protector. Follow Fernox installation instructions. Failure to use Fernox F3 or F5 cleaner and F1 protector could void the warranty for all waterside components.
  • Page 45: Starting Up The Boiler

    REGULATION INSTRUCTIONS 4.5 Starting up the boiler Once the system has been filled, proceed as follows: Table n°1  Check that the exhaust flue is free of obstructions and correctly Gas type connected to the boiler;  Switch on the power supply to the Natural Gas - G20 9.18 appliance;...
  • Page 46: Regulating The Appliance (Authorized Personnel)

    REGULATION INSTRUCTIONS 5. REGULATING THE APPLIANCE 5.1 Parameters table PARAMETER TYPE OF OPERATION PARAMETER VALUE FUNCTION N° 01 = 18 KW 04 = 34 kW Selects the model of boiler 00-06 05 = 50 kW All other numbers NA 00 = NA 01 = PCC 34 02 = PCI 18/8, PCI 34/20 Selects the type of boiler...
  • Page 47 REGULATION INSTRUCTIONS 00 = Disabled (default) Sets the 0-10V industrial bus piloting 00-02 01 = Flow temperature control mode 02 = Burner output control mode Central heating minimum set point 20 - 40 Displayed in °C Central heating maximum set point 40 - Displayed in °C D.H.W maximum set point...
  • Page 48 REGULATION INSTRUCTIONS 5.2 Setting the parameters To modify the pre-set values of the parameters reported in the previous table, open the parameter settings menu as follows: 1. Place mode selection button ‘ ’ in OFF position, visualized by symbol; 2. Keep pressed ‘ ’...
  • Page 49: Setting The Parameters

    REGULATION INSTRUCTIONS 5.3 Setting the parameters PARAMETER P00 – SELECTS THE MODEL OF BOILER To enter the parameters menu, follow the previously described procedure (see paragraph 5.2 ‘Accessing the parameters menu’ - steps 1-4). 5. Use ‘ ’ and ‘ ’...
  • Page 50 REGULATION INSTRUCTIONS PARAMETER P03 – SETS THE CENTRAL HEATING TEMPERATURE To enter the parameters menu, follow the previously described procedure (see paragraph 5.2 ‘Accessing the parameters menu’ - steps 1-4). 5. Use ‘ ’ and ‘ ’ buttons (D.H.W temperature setting) modify the value of the parameter: 00 = standard (95-185°F) 01 = reduced (77-113°F) for under-floor heating...
  • Page 51 MAINTENANCE INSTRUCTIONS PARAMETER P06 – D.H.W PRIORITY FUNCTION This parameter is used to maintain the diverter valve on D.H.W mode for a time equal to the post-circulation, keeping hot the secondary heat exchanger To enter the parameters menu, follow the previously described procedure (see paragraph 5.2 ‘Accessing the parameters menu’...
  • Page 52 MAINTENANCE INSTRUCTIONS PARAMETER P09 – D.H.W/STORAGE CYLINDER PUMP OVERRUN TIMER This parameter is used to set the pump functioning time, in D.H.W mode, after closing the water tap To enter the parameters menu, follow the previously described procedure (see paragraph 5.2 ‘Accessing the parameters menu’ - steps 1-4) Use ‘+’...
  • Page 53 MAINTENANCE INSTRUCTIONS PARAMETER P12 – PARAMETER P12 - SETS THE MINIMUM FAN SPEED (CENTRAL HEATING) This parameter is used to set the minimum fan speed in heating mode, which corresponds to the minimum burner output during a heating mode request. To enter the parameters menu, follow the previously described procedure (see paragraph 5.2 ‘Accessing the parameters menu’...
  • Page 54 MAINTENANCE INSTRUCTIONS PARAMETER P15 – LEGIONELLA PREVENTION FUNCTION (For storage boilers only) To enter the parameters menu, follow the previously described procedure (see paragraph 5.2 ‘Accessing the parameters menu’ - steps 1-4) Use ‘+’ and ‘-’ buttons (D.H.W temperature setting) to modify the value of the parameter 00 = Off 01 = On (default)
  • Page 55 MAINTENANCE INSTRUCTIONS PARAMETER – SETS TEMPERATURE MEASUREMENT UNIT This parameter is used to set the temperature measurement unit displayed: Celsius ( ) or Fahrenheit ( ) degrees. To enter the parameters menu, follow the previously described procedure (see paragraph 5.2 ‘Accessing the parameters menu’ - steps 1-4) Use ‘+’...
  • Page 56 MAINTENANCE INSTRUCTIONS PARAMETER 20 - CENTRAL HEATING MAXIMUM SET POINT This parameter is used to set the central heating maximum user set point. To enter the parameters menu, follow the previously described procedure (see paragraph 5.2 ‘Accessing the parameters menu’ - steps 1-4) Use ‘+’...
  • Page 57 MAINTENANCE INSTRUCTIONS PARAMETER P23 – MODULATING PUMP MINIMUM SPEED (not applicable) This parameter is used to set the minimum modulating pump speed during a heating mode request. To enter the parameters menu, follow the previously described procedure (see paragraph 5.2 ‘Accessing the parameters menu’ - steps 1-4) Use ‘+’...
  • Page 58: Gas Data

    NATURAL GAS – GAS A LIQUID PROPANE GAS – GAS E Heating Value (BTU/Cubic Feet) 2516 BTU/FT³ 1000 “wc Nominal supply gas pressure Heating Power (kW) – Fan frequency (Hz) diagram PCC 34-H, PCH 34B-H & PCI 34/20-H LP Gas Nat Gas...
  • Page 59: Converting The Boiler To A Different Gas Type

    The conversion of this boiler from burning natural gas to LPG, or vice versa, must be carried out exclusively by professionally qualified personnel, registered in accordance with current legislation and authorized by Pensotti LLC. It is necessary to use a properly calibrated, electronic combustion analyzer.