MAINTENANCE INSTRUCTIONS
PARAMETER P06 – D.H.W PRIORITY FUNCTION
This parameter is used to maintain the diverter valve on D.H.W mode for a
time equal to the post-circulation, keeping hot the secondary heat exchanger
To enter the parameters menu, follow the previously described procedure
(see paragraph 5.2 'Accessing the parameters menu' - steps 1-4)
5.
Use '+' and '-' buttons (D.H.W temperature setting) to modify the value of
:
the parameter
00 = Off (default)
01 = On
6.
Press mode selection button
.
parameter operative
7.
To exit from the parameters menu, press simultaneously 'i' and 'R'
.
buttons
PARAMETER P07 – CENTRAL HEATING TIMER
This parameter is used to set the minimum time in which the burner is kept
switched off, once the heating flow temperature has exceeded the
temperature set by the user
To enter the parameters menu, follow the previously described procedure
(see paragraph 5.2 'Accessing the parameters menu' - steps 1-4)
5.
Use '+' and '-' buttons (D.H.W temperature setting) to modify the value of
the parameter within the prescribed limits
):
seconds
min = 00
max = 90
Example:
90 = 90 x 5 sec = 450 sec (7,5 min)
36 = 180 sec = 3 min
The default value is
6.
Press mode selection button
.
parameter operative
7.
To exit from the parameters menu, press simultaneously 'i' and 'R'
.
buttons
PARAMETER P08 – CENTRAL HEATING PUMP OVERRUN TIMER
This parameter is used to set the pump functioning time, in heating mode,
after switching off the main
.
thermostat
To enter the parameters menu, follow the previously described procedure
(see paragraph 5.2 'Accessing the parameters menu' - steps 1-4)
5.
Use '+' and '-' buttons (D.H.W temperature setting) to modify the value of
the parameter within the prescribed limits
):
seconds
min = 00
max = 90
Example:
90 = 90 x 5 sec = 450 sec (7,5 min)
36 = 180 sec = 3 min
The default value is
6.
Press mode selection button
.
parameter operative
7.
To exit from the parameters menu, press simultaneously 'i' and 'R'
.
buttons
to confirm and to render the new
.
(
displayed in multiples of 5
to confirm and to render the new
burner for the intervention of the room
(
displayed in multiples of 5
to confirm and to render the new
.
.
.
.
46