3.6 Piping Diagram – Primary Secondary Piping
Pensotti requires the
installation of a pressure
reducing valve & backflow
preventer with all Solenne
Series boilers.
Dirt / Scale Separation
Along with the application of our Fernox commissioning kit
Pensotti highly recommends the installation of a dirt separator
in the return piping of all Solenne Series boiler models. Follow
the manufacturer's instructions when installing these devices.
This piping diagram is an example for illustrative purposes only. It is not designed to be
used as a piping schematic.
*Max. 4 pipe diameters between tees
*External Low Water Cut-Off if required by local code
*Tempering Valve May be Required – Consult Local Codes
*Must leave at least 15" of straight pipe on either side of closely spaced tees
INSTALLATION INSTRUCTIONS
21