I2C Interface: I/O And Power Supervision - Siemens NK8000 Series Installation, Configuration & Operation

Hide thumbs Also See for NK8000 Series:
Table of Contents

Advertisement

3.1.7
Building Technologies
CPS Fire Safety

I2C interface: I/O and power supervision

This interface allows for a direct support of:
Direct digital input/output:
One or two DF8040 (CF9040) input modules
One DF8020 (CF9020) output module
Power supply supervision:
One DF8090 power supply supervision module
All modules can be installed on the DIN-rail, next to NK822x unit.
DF8020
DF8020 is a module providing 8 relay outputs, NO or NC.
DF8040
DF8040 is a module providing 8 inputs, which can be normally open or normally
closed and driven by dry contacts or open collector signals
See NK822x hardware installation [➙ 36] for more information on the connection of
I/O modules to the NK822x
DF8090 Power Supply Supervision
DF8090 is a module designed for monitoring a 12V DC power supply. It can detect
the conditions listed below, shown on the DF8090 local panel and report them to
NK822x, and in turn to management station (see the following):
Mains failure (no 220VAC)
Battery low
Power supply failure (trouble with AC/DC converter)
Battery protection fuse blown (internal micro-fuse type MSF 3.15A/250V)
PW
MAINS
1
AC/DC
LOW BATT
BATT FUSE
DF8090 front panel
Item
Description
1
LEDs.
2
I
C connector to I/O modules.
2
NK822x power connections
See figure
for the NK822x power connections using the power supervision module.
Structure and functions
NK822x hardware
2
(see NK822x hardware installation [➙ 36])
3
23
A6V10062437_a_en
30.01.2019

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nk8222Nk8225Nk8223Nk8232Nk8235Nk8231

Table of Contents