Serial Interfaces - Siemens NK8000 Series Installation, Configuration & Operation

Hide thumbs Also See for NK8000 Series:
Table of Contents

Advertisement

Structure and functions
3
NK822x hardware
3.1.4
20
Building Technologies
CPS Fire Safety
1
NK822x internal DIP switch and jumpers
Item
Description
1
DIP-Switches
2
Reset button
3
JP6: enable LON resistor.
4
Tamper switch
5
JP3: disable tamper or connect to external tamper.

Serial interfaces

NK8223 / NK8225: although the maximum number of serial lines is 4, they are not
always used. There are two serial lines available on the base module and two on
an expansion module.
NK8222: this model is equipped with two serial lines only available on the base
module.
Note: In all modules, the first serial port can be configured as an RS232 interface
using connector COM1 or as an RS485 interface using connector CN4.
All lines are fully RS232 compliant and have EMC/ESD protection.
No galvanic isolation is provided; all serial lines have a common ground.
2
3
A6V10062437_a_en
4
5
30.01.2019

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nk8222Nk8225Nk8223Nk8232Nk8235Nk8231

Table of Contents