5.4

Secondary wiring

Terminal assignment
 (page 8-1)
Cross-sections
Connection type
Screw clamp terminal
(SIGUT system)
Spring clamp terminal
Ring terminal system
1) Use of wire end ferrules (crimp style) is possible
1 x up to14 AWG tube-type without insulating sleeve
1 x up to 16 AWG tube-type with insulating sleeve
2 x up to 16 AWG tube-type with insulating sleeve, twin wire end ferrule
2) 2 x up to 14 AWG tube-type without insulating sleeve
2 x up to 16 AWG tube-type with insulating sleeve
5 – 27
Strip conductors
7 mm
1/4"
7 mm
1/4"
14 - 16 AWG
Recommendation:
AMP, PIDG series
Catalog No. 50881
10 AWG
Recommendation:
Siemens part
Catalog No. WL10RL
1 x
20 -14 AWG1)
2
1)
0.5 - 2.5 mm
1)
20 -14 AWG
2
1)
0.5 - 2.5 mm
2 x
20 -14 AWG 1)
2 1)
0.5 - 1.5 mm
2)
20 -14 AWG
2 2)
0.5 - 2.5 mm