Mounting Frame size II 3000 A and Frame size III
(1)
1
Remove 6 screws from the lower side of the sensor covers
2
Locate the connectors on the breaker terminals and secure them with screws M12, nuts and belleville washers. Screw orientation:
Nuts between terminals (facing each other).
Do not tighten yet.
Upper terminals
Assemble the steel bushings (3) with screws M6x75 (5) and belleville washers.
3
Do not tighten yet.
4
Push the connector against the steel bushings (3).
5
Tighten the center screws M12 (2) to the specified torque (85 Nm / 60 ft-lb)
6
Remove the steel bushings (3) and screws.
7
Tighten the outer screws M12 (5) to the specified torque (85 Nm / 60 ft-lb)
8
Assemble the steel bushings (3) and scews (5) again and tighten to the specified torque (8 Nm / 70 lb-in)
Lower terminals
9
Assemble the support (6) to the connector using self-tapping screws M6x25 (1) and tighten to the specified torque (8 Nm / 70 lb-in).
10 Assemble screws M6 (4) with belleville washers.
Do not tighten yet.
11 Push the connector and support against the circuit breaker housing.
12 Tighten the center screws M12 to the specified torque (85 Nm / 60 ft-lb). Tool access via the holes in the support.
13 Remove the M6 screws (4).
14 Tighten the outer screws M12 to the specified torque (85 Nm / 60 ft-lb). Tool access via the holes in the support.
15 Mount the M6 screws (4) again and tighten to the specified torque (8 Nm / 70 lb-in).
NOTE
Store or pack the frame on a pedestal of about 2" height, to protect the extending lower ends of the load connectors from
being damaged.
(6)
(4)
(3)
(2)
(page
5-13).
(5)