Ground-Fault Protection Modules - Siemens UL 489 Operating Instructions Manual

Hide thumbs Also See for UL 489:
Table of Contents

Advertisement

Replacing Rating Plug
Circuit breaker may trip.
If the trip settings are changed while the breaker is closed (and under load) the breaker may trip.
Adjust parameters only when the circuit breaker is in the open position.
9.1.8

Ground-fault protection modules

WL trip units can be optionally equipped with modules that add ground fault protection. The modules provide either an alarm-only function
or alarm-and-trip functionality.
The modules can be added or removed as necessary in the field.
 (page 9-12)
Settings are found on
The following combinations are possible:
Trip unit
ETU745
ETU776
The following options exist for ground-fault detection:
- Vector sum of the three phase currents plus neutral, if a neutral sensor is connected (residual sensing).
- Direct measurement of the ground-fault current using a separate 1200 A : 1 A iron-core ground fault sensor.
The direct-sense input to the trip unit has the following current-carrying capability:
- max. 1 A continuous
- max. 5 A for 0.5 sec.
Note
If the circuit breaker is applied in a 4-wire system, and residual ground
fault protection is desired, it is strongly recommended that a WL neutral
sensor (WLNCT2, WLNCT3) be used on the neutral to facilitate the 
correct vector-summation of the phase currents with the neutral. Failure
to apply a neutral sensor may result in erroneous GF alarm and trips.
Note
Output of alarms and messages is possible via COM and c
modules.
9 – 44
1
OPEN
Ground-fault protection module
GFM A 745 (alarm only)
GFM AT 745 (alarm and trip)
GFM A 776 (alarm only)
GFM AT 776 (alarm and trip)
NOTICE
3
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents